Periodic checklists, Maintenance periodic checklists – Trane SCWH User Manual

Page 29

Advertising
background image

PKG-SVX14A-EN

29

Periodic Checklists

Monthly Checklist

The following checklist provides the

recommended maintenance schedule to

keep the unit running efficiently.

WARNING

Hazardous Voltage!

Disconnect all electrical power including

remote disconnects before servicing

unit. Follow proper lockout/tagout

procedures to ensure power cannot be

inadvertently energized. Failure to

disconnect power before servicing could

result in death or serious injury.

1. Inspect unit air filters. Clean or replace

if airflow is blocked or if filters are dirty.

2. Inspect coils for icing. Icing on the coils

may indicate low airflow supply,

restricted airflow from dirty fins.

3. Check the fan belt condition and

tension. Adjust tension if belt is floppy or

squeals continually.

4. Check and record operating pressures.
Semi-Annual Maintenance

1. Verify the fan motor is properly aligned

and bolted tight to the motor frame.

2. Lubricate fan bearings.

3. With power disconnected, manually

rotate the fan wheel to check for

obstructions in the housing or

interference with fan blades. Remove

obstructions and debris. Center the fan

wheel if necessary.

4. Check the fan assembly sheave

alignment. Tighten set screws to their

proper torques.

Note: Perform this procedure monthly if

the unit is in a coastal or corrosive

environment.

Annual Maintenance

Check and tighten all set screws, bolts,

locking collars and sheaves.

1. Inspect, clean, and tighten all electrical

connections.

2. Visually inspect the entire unit casing

for chips or corrosion. Remove rust or

corrosion and repaint surfaces.

3. Visually check for leaks in refrigerant

piping.

4. Inspect fan, motor, and control

contacts. Replace badly worn or eroded

contacts.

Maintenance

periodic

checklists

5. Inspect the thermal expansion valve

sensing bulbs for cleanliness, good

contact with the suction line, and

adequate insulation from ambient air.

WARNING

Live Electrical Components!

During installation, testing, servicing,
and troubleshooting this equipment, it
may be necessary to work with live
electrical components. Have a
qualified licensed electrician or other
individual who is properly trained in
handling live electrical components
perform these tasks. Failure to follow
all electrical components could result
in death or serious injury.

WARNING

Rotating Components!

During installation, testing, servicing
and troubleshooting of this product it
may be necessary to measure the
speed of rotating components. Have a
qualified or licensed service individual
who has been properly trained in
handling exposed rotating
components, perform these tasks.
Failure to follow all safety precautions
when exposed to rotating
components could result in death or
serious injury.

Advertising
This manual is related to the following products: