Configuration, Operation, Set configuration dip switches – Tripp Lite PowerVerter 200812163 User Manual

Page 5: Group a dip switches (all models)

Advertising
background image

5

Configuration

set Configuration DIP switches

Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation

depending on your application. Refer to the appropriate section to review the instructions for your specific model.

INPUT C/B 10A

OUTPUT C/B 12A

B4

B3

B2

B1

A4

A3

A2

A1

Group B Dip Switches

Group A Dip Switches

group A DIP switches (All Models)

Using a small tool, configure your Inverter/Charger by setting the four Group A DIP Switches (located on the front panel of your unit; see

diagram) as follows:

A2

Operation

(continued)

resetting Your Inverter/Charger to restore AC Power

Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your

electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to “DC OFF” and remove some of the connected electrical load (i.e., turn off some of the

AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to

either “AUTO/REMOTE” or “CHARGE ONLY.”
Output Circuit Breaker Reset: If tripped, remove a portion of the load, wait one minute and then press breaker button to reset.

Select Low AC Input Voltage Point for

Switching to Battery—OPTIONAL*

Voltage and Level

120V Models 230V Models

Switch Position

A 105V

201V

A4 Up & A3 Up

B 95V

182V

A4 Up & A3 Down

C 85V

163V

A4 Down & A3 Up

D 75V

144V

A4 Down & A3 Down

(factory setting)

A1

A2

A3

A4

A1

A2

A3

A4

A1

A2

A3

A4

A1

A2

A3

A4

A3

A4

A1

* Most of your connected appliances and equipment will perform adequately when your
Inverter/Charger's Low AC Voltage Input Point (DIP Switch #3 and #4 of Group A) are set
to Level B (95V for 120V Models/182V for 230V Models). However, if the unit frequently
switches to battery power due to momentary low line voltage swings that would have little
effect on equipment operation, you may wish to adjust this setting. By decreasing the Low
AC Voltage Input Point, you will reduce the number of times that your unit switches to
battery due to voltage swings.

Select Battery Type—REQUIRED

CAUTION: The Battery Type DIP Switch setting must match
the type of batteries you connect, or your batteries may be
degraded or damaged over an extended period of time. See
"Battery Selection" section for more information.

Battery Type

Switch Position
AGM/Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

Select Charger Enable/Inhibit

Switch is preset to ENABLE, which

permits continuous battery charging.

If you are connecting your unit to

batteries with a separate charger, you may

set this switch to INHIBIT to disable its

built-in charger to prevent overcharging.

Battery Type

Switch Position

Inhibit

Up

Enable

Down (factory setting)

A1

A2

A3

A4

A1

A2

A3

A4

ENABLE

INHIBIT

Level A

Level B

Level C

Level D

Advertising