TE Series

Digital Solid State Soft Starters 18 – 1250A

78

ƒ

IMPORTANT NOTE: When F030 or F031 is changed in program mode, the timer
will not respond to the new settings until after control power has been cycled (off
and back on again).

F032 = Time Clock Controller (TCC)

Factory Setting = 0 (One Shot)
Range = 1 - 8 settings
This function is used to select the operating mode of the 24hr /
7 Day Time Clock Controller (TCC).

F032 = 0 operates the SEC in a “One-Shot” mode (factory
default setting). When set to 0, the Process Timer (F030)
responds only to each NEW hard-wired START input command.
Use this setting to allow the Process Control Timer to
operate without the TCC.
For safety purposes when using 2 wire control systems in this
mode only, if power fails and the START/RUN command is
present when power is restored, the starter will ignore this
command until the input is cycled Off and back On (terminals
TB1-1 and 3 are opened and reclosed).

For automatic operations,
F032 can also set the number of
days in which the TCC will repeat a Start Event Cycle (SEC).
Each Start Event Cycle consists of from 1 to 7 Start Events as
programmed in F033 through F039 below. Start Events can be
non-sequential (see NOTE below).
F032 = 1 operates the SEC every day of the week.
F032 = 2 operates the SEC every 2 days (every other day)
F032 = 3 operates the SEC every 3

rd

day.

F032 = 4 operates the SEC every 4

th

day.

F032 = 5 operates the SEC every 5

th

day.

F032 = 6 operates the SEC every 6

th

day

F032 = 7 operates the SEC 1 day per week.
F032 = 8 operates the SEC for a single 24HR event, non-
repeating. Use this for testing or for “walk away” operations that
need to run after you leave but not again.

Start Event Cycles allow the use of a Start Command (2-wire or
3-wire) ONLY AFTER the time of the Start Event has passed
(logic state AND). In a 3-wire control system, this is similar to
having an Enable switch in series with the Stop button. In a 2-
wire control system, this is similar to having and Enable
contacts in series with the Run contact. The Stop Button (or
opening the Run contact) will always work to shut down the TE
Series
starter. If F032 is set to anything other than 0, the
normal Start – Stop functions will no longer work except as
shown above.

Each Start Event is a timed operation based on the Process
Timer settings in F030 above.

CAUTION

If F030 = 0 (Disabled), the TCC will be ignored. So if F032 = 1-8 and F030 = 0, the
starter will not operate!
Make sure that if F030 = 0, F032 = 0 as well.