TE Series

Digital Solid State Soft Starters 18 – 1250A

80

Fn#

Function

Type

Setting

Function Description / Range

Timer

Initiated

By…

Motor
Starts

When…

Motor
Stops

When…

Timer
Reset

When…

F030

Process

Control

Timer

Mode

0

No Process Control Timer operation (default setting from factory)

1

Minimum (Batch) Run Timer
(works the same with or without TCC
control)

Start

command

and/or

TCC

Start

command

Time

Expires,

Trip, or

Stop

Command

Time

Expires +

Stop

command

only

2

Permissive Run Timer, without TCC
(F032 =0, “One Shot”)

Start

command

Start

command

Time

Expires

Permissive Run Timer, with TCC
(F032 = 2 thru 8)

TCC Start

Event

only

Next SEC

only

F031

Process

Timer
Value

Run

Time

Value

Timer value setting used by F030
Range: 1 – 9999 minutes (166.65
hours)

--- ---

Per F030

setting

F032

24 hr /
7 day

Time Clock
Controller

0

One-Shot, follows Start command only

Start

command

Start

command

Per F030

setting

Per F030

setting

1

Loop the Start Even Cycle (SEC) daily

24hr Real

Time

Clock on

day of

program

change

Per F030

setting

Per F030

setting

Continuous

unless

program is

changed

2

Loop the 24hr SEC every other day

3

Loop the 24hr SEC every 3

rd

day

4

Loop the 24hr SEC every 4

th

day

5

Loop the 24hr SEC every 5

th

day

6

Loop the 24hr SEC every 6

th

day

7

Loop the 24hr SEC one day per week

8

Single 24hr SEC, without repeating
(until programmed again)

Change of

Program

F033 Event

#1

Start

time

24hr TCC Start Time for Event #1

F032 =1-8

Continuous

unless

program is

changed

F034 Event

#2

Start

time

24hr TCC Start Time for Event #2

F035 Event

#3

Start

time

24hr TCC Start Time for Event #3

F036 Event

#4

Start

time

24hr TCC Start Time for Event #4

F037 Event

#5

Start

time

24hr TCC Start Time for Event #5

F038 Event

#6

Start

time

24hr TCC Start Time for Event #6

F039 Event

#7

Start

time

24hr TCC Start Time for Event #7

Chart APP 4.1

Process Timer and TCC Operations Logic Chart


ƒ

NOTE:
These functions may interact with the Coast Down Lockout (F048),
Stars-per-Hour Lockout (F049), Minimum Time Between Starts
(F050), Auto-Reset (F052) and Restart Delay Time (F028) functions
if enabled. Be sure to read and understand descriptions of those
functions, then check settings before using the Process Control
Timer.