- 16 -

5. How to calibrate the air probe

If the actual cellar temperature differs from the displayed temperature, set ot =
actual cellar temperature minus displayed temperature.

6. How to adjust defrost cycle

1) I

n case

the cooling unit does not stop, t

he parameters FnC = C-n, idF =4 and

MdF = 30 can be used to cycle off.

2) I

n case there is excessive frost, the parameters FnC = C-y, idF = 6 and MdF =

20 can be used to avoid defrost.


7. How to adjust the humidity

The parameter Fon is used to adjust the humidity in the wine cellar. Higher Fon
results in higher relative humidity.

Use a separate hygrometer to monitor the

humidity.

8. How to set alarm call

1) S

peech notice will be sent to your phones when the cellar temperature is ALU

higher or ALL lower than the set-point Set.

2) In order to test the call function, set parameters Ald = 0 and dAO = 0. After
testing, set Ald = 60 and dAO = 23.

9. How to set low cellar temperature heater

The heater turns on at set-point SAA minus regulation differential Shy; the
heater turns off at heater set-point SAA.

NOTES:

• Use a forced air heater to warm up the wine cellar.

• If there is a thermostat on the heater, bypass it or set the thermostat at the

highest level.

• If the heater runs more than 10 A current, use a 120VAC coil contactor.

10. Manual Defrost

Press the DEF key for more than 2 seconds and a manual defrost will start.

11. Parameter Programming

1) Press the SET +

keys for more than 3 sec until the “°C” or “°F” LED starts

blinking, then release the keys.
2) Press again the SET +

keys for more than 7sec until the Pr2 label will be

displayed, then release the keys. The first parameter Hy will be displayed.