York E1FB240 User Manual

Page 4

Advertising
background image

CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF

54" (when lifting from the compressor end of the
unit) and a MINIMUM OF 42" (when lifting from the
front or rear of the unit).

Remove the nesting brackets from the four corners on top of
the unit. All screws that are removed to take these brackets off
must be replaced on the unit.

CLEARANCES

All units require certain minimum clearances for proper opera-
tion and service. Refer to Figure 4 for these clearances.

WARNING: Do not permit overhanging structures or shrubs

to obstruct air discharge.

Additional height may be required for snow clearance if winter
operation is expected.

COMPRESSOR CRANKCASE HEATER

The compressor is equipped with a crankcase heater to pre-

vent refrigerant from mixing with crankcase oil during the

“OFF” cycle. The heaters will be energized when the com-

pressor is not running providing the unit disconnect switch is

closed.

CAUTION: Do not attempt to start the compressor without at

least eight hours of crankcase heat or compressor
damage will occur.

If a unit has just been installed or the unit disconnect switch has
been open for a long period of time, move the system switch on
the room thermostat to the “OFF” position before closing the
unit disconnect switch. Eight hours of crankcase heat are re-
quired to drive the liquid refrigerant out of the compressor bef-
ore the compressor can be started.

POWER AND CONTROL WIRING

Install electrical wiring in accordance with the latest National
Electrical Code (NFPA Standard No. 70) and/or local regula-

tions. The unit should be grounded in accordance with these

codes.

POWER WIRING

Check the voltage of the power supply against the data on

the unit nameplate. Check the size of the power wire, the

disconnect switch and the fuses against the data in Table 3.

NOTE: Copper conductors must be installed between the dis-

connect switch and the unit.

Refer to Figure 4 for the location of the power wire access

opening through the front of the unit. This opening will re-

quire a field-supplied conduit fitting.

The field-supplied disconnect switch must be suitable for an
outdoor location. Although it should be installed near the unit,
do NOT secure it to the unit cabinet.

Refer to Figure 3 for typical field wiring.

CONTROL WIRING

Refer to Figure 4 for the location of the control wire access
opening through the front of the unit.

Route the necessary low voltage control wires from terminal

block TB2 of the unit control box through this access open-

ing to the indoor unit and to the room thermostat. Refer to

Figure 3 for typical field wiring.

The room thermostat should be mounted about 5 feet above

the floor and located where it will be exposed to normal room

air circulation. Do not locate it on an outside wall, near a

supply air grille, or where it may be affected by sunlight

4

Unitary Products Group

035-16192-001-A-1001

O

O

O

O

O

O

O

O

O

O

FIG. 2 - TYPICAL RIGGING

5 ft.

MIN

DESCRIPTION

UNIT MODEL

EFB180

EFB240

Compressor

1

Rating - (Qty) Tons

(2) 7-1/2

(2) 10

Fans

Quantity

2

2

Diameter - inches

24

26

Blades/Pitch (°)

3/32

3/36

Nominal CFM

10862

11395

Fan Motors

2

HP

1

1

RPM

1100

1100

Rows Deep X Rows High

2 X 40

2 X 40

Finned Length - inches

130

130

Face Area - square feet

36.11

36.11

Tube(Copper) OD - inches

3/8

3/8

Fins (Aluminum) per inch

18

20

Holding Charge

(Sys 1 / Sys 2)

3

1-0/1-0

1-0/1-0

Operating Charge

(Sys 1 / Sys 2)

4

16-8/17-8 19-0/19-0

Shipping

970

1020

Operating

980

1040

1

These compressors are fully hermetic.

2

The ball bearing, 48 frame, single phase condenser fan motor have internal

protection and are directly connected to the condenser fins. Motor rotation is
counterclockwise when viewing the lead end, which is opposite the shaft end.

3

The amount of charge in the unit as shipped from the factory.

4

Total operating charge for the condensing unit, matching indoor unit, and 25 feet

of interconnecting pipe.

TABLE 2 - PHYSICAL DATA

Advertising
This manual is related to the following products: