Table 3 - electrical data, Fig. 3 - typical field wiring – York E1FB240 User Manual

Page 5

Advertising
background image

Unitary Products Group

5

035-16192-001-A-1001

Y1

W1

Y2

C

R

X

O

HC

O

HR

G

W1

Y2

Y1

R
C

X

R
C

Y1
Y2

O

W1

X

G

6*

6*

TERMINALS ON:

- Supply Air Blower Motor

Contactor 10M

OR

- Terminal Block Electric

Heat Control Box

GROUND SCREW

"Heat Pump only" Units

GROUND LUG

Units with Electric

Heat Accessory

3-PHASE LINE VOLTAGE POWER SUPPLY

Refer to electrical data to size the power

wiring, disconnect switch and overcurrent

protection*.

USE COPPER CONDUCTORS ONLY

TERMINALS ON

COMPRESSOR

CONTACTORS 1M &3M

GROUND

LUG

INDOOR UNIT

OUTDOOR UNIT

TERMINALS ON HEAT

PUMP THERMOSTAT

1

1

Control wiring (24-volt)

refer to electrical data

to determine the proper

wire size.

RLA LRA RLA LRA

Qty FLA (Each) Qty FLA (Each)

80 @ 208 V
88 @ 230 V

126 @ 208 V
140 @ 230 V

8 AWG

142

6 AWG

224

104 @ 208 V
115 @ 230 V
165 @ 208 V
182 @ 230 V

8 AWG

111

6 AWG

176

Model Number

Compressors

Outdoor Fan Motors

Minimum

Circuit

Ampacity

System 1

System 2

System 1

System 2

Power Supply

Power Supply

Maximum

Fuse

Size



Minimum

Wire Size

AWG

Maximum

Wire Length

feet

!

Minimum

Disconnect

Amps

E1FB180A25 208/230-3-60 32.1 195.0 32.1 195.0 208/230-1-60 1

4.7

1

4.7

81.6

90

4 AWG

100

2 AWG

E1FB180A46

460-3-60

16.4 95.0 16.4 95.0

460-1-60

1

2.5

1

2.5

41.9

45

60

E1FB240A25 208/230-3-60 42.0 239.0 42.0 239.0 208/230-1-60 1

4.7

1

4.7

103.9

110

2 AWG

150

0 AWG

E1FB240A46

460-3-60

19.2 125.0 19.2 125.0

460-1-60

1

50

60

2.5

1

2.5

48.2

TABLE 3 - ELECTRICAL DATA

1

Maximum fuse or maximum circuit breaker (HACR type per NEC).

2

Based on three 75°C insulated copper conductors in conduit and ambient of 30°C.

3

Based on 5% voltage drop, since unit controls are powered off the unit supply. Two minute time delay between system 1 and system 2.

WIRE IN ACCORDANCE WITH LOCAL
AND NATIONAL ELECTRICAL CODES

FIG. 3 - TYPICAL FIELD WIRING

1

Only required when an electric heat

accessory is used.

*All outdoor units and all heat pump only indoor units

require dual element, time delay fuses. Circuit
breakers can be used in lieu of fuses for indoor units
with an electric heat accessory.