FIG.12 - UNIT DIMENSIONS & CLEARANCES (F3EH090 & F4EH120)

All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.

ACCESSORIES

ELECTRIC HEATER - Add 14-1/4" to unit height when used.

SUPPLY AIR PLENUM - Add 27-1/2" to unit height when used.

BASE - Add 20" to unit height when used.

CLEARANCES

Side with RETURN AIR opening

24"

Side with SUPPLY AIR opening

24"

1

Side with PIPING CONNECTIONS

52"

2

Side opposite PIPING CONNECTIONS

12"

Side with access for both POWER & CONTROL WIRING

3

Bottom

4

1

Overall dimension of the unit will vary if an electric heater, a

supply air plenum or a base is used.

2

This dimension is required for removal of the coil. Only 26" is

required for normal servicing.

3

Although no clearance is required for service and operation,

some clearance may be required for routing the power wiring
and the control wiring.

4

Allow enough clearance to trap the condensate drain line.