Model

Accessory

Static Resistance, IWG

BLOWER CFM

2400

2700

3000

3300

3600

F3EH090

Electric

Heat

10 KW

0.01

0.01

0.01

0.02

0.02

16 KW

0.01

0.02

0.02

0.03

0.04

26 KW

0.03

0.04

0.05

0.06

0.07

36 KW

0.05

0.07

0.08

0.10

0.11

Supply Air Plenum

0.03

0.03

0.04

0.05

0.06

Return Air Grille

0.02

0.03

0.04

0.05

0.06

BLOWER CFM

3200

3600

4000

4400

4800

F4EH120

Electric

Heat

10 KW

0.02

0.02

0.03

0.03

0.04

16 KW

0.03

0.04

0.05

0.06

0.07

26 KW

0.06

0.07

0.09

0.11

0.13

36 KW

0.09

0.11

0.14

0.17

0.20

Supply Air Plenum

0.05

0.06

0.07

0.08

0.10

Return Air Grille

0.05

0.06

0.07

0.08

0.10

TABLE 6 - ACCESSORY STATIC RESISTANCE (IWG)

(To be included with Duct System Static Resistance)

CONTROL WIRE SIZING

Wire Size

Maximum Total

Circuit Length

(Feet)

#19 Solid

130

#18 Solid

170

#18 Stranded

180

#16 Stranded

270

#14 Stranded

455

#12 Stranded

730

To determine the total circuit length, add the following distances:

1 - Outdoor Unit to Indoor Unit ___________

2 - Indoor Unit to Thermostat ____________

3 - Thermostat to Indoor Unit ____________

4 - Indoor Unit to Outdoor Unit ___________

5 - Outdoor Unit to Elec. Heater __________

Total Circuit Length __________

Model

Motor HP*

Blower RPM

Adjustable Motor Pulley

Fixed Blower Pulley

Belt

Pitch Dia.

(Inches)

Bore

(Inches)

Pitch Dia.

(Inches)

Bore

(Inches)

Designation

Pitch Lg.

(Inches)

60 Hz

F3EH090

1-1/2

655 - 880

2.8 - 3.8

7/8

7.5

1

A36

37.3

F4EH120

2

700 - 950

7.0

50 Hz

F3EH090

1-1/2

542 - 732

7.5

F4EH120

2

581 - 786

7.0

*

These factory-mounted motors are wired for a 460V power supply. Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads for a
208 or 230 volt power supply.

TABLE 7 - BLOWER MOTOR AND DRIVE DATA

Blower

Motor

HP

Power

Supply

FLA

Max. Fuse

Size,

1

AMPS

Max. Wire

Length

2

(Ft.)

F3EH090

1-1/2

208-3-60

5.3

10

207

230-3-60

5.8

10

209

460-3-60

2.7

5

897

380-3-50

3.3

5

606

415-3-50

4.0

5

546

F4EH120

2

208-3-60

7.5

10

146

230-3-60

6.8

10

178

460-3-60

3.4

5

712

380-3-50

4.0

5

500

415-3-50

4.5

5

485

NOTE: Refer to Form 550.13-N10.1 for electrical data on units equipped with an electric

heat accessory.

1

Dual element, time delay fuses.

2

Based on three 60

°

C, 14 AWG, insulated copper conductors in steel conduit, a 3% voltage

drop.

TABLE 8 - ELECTRICAL DATA