WARNING: Do not permit overhanging structures or shrubs to

obstruct air discharge.

Additional height may be required for snow clearance if winter
operation is expected.

VERTICAL / HORIZONTAL INSTALLATION

These indoor units are shipped for vertical installation with ver-
tical air discharge as shown in Figure 2(A) but may be con-
verted for horizontal installation as shown in Figure 2(B) by
interchanging the solid bottom panel and the return air duct
flange.

DUCT CONNECTIONS

Design and install all ducts in accordance with all national
and/or local codes.

Ducts should be sized no smaller than the duct flanges on the
unit or the electric heater (if used). Refer to the unit dimensions
(Fig. 12) and the heater detail (Fig. 3) for these sizes. Refer to
Form 035-16602-002 for installation instructions on the electric
heater.

Use flexible fiber glass or plastic cloth collars or other nonflam-
mable material at the unit duct connections to minimize the
transmission of noise and vibration.

Insulate all ductwork running through unconditioned areas to
prevent moisture condensation and to provide more economi-
cal operation.

The return air duct flange is factory-mounted on the front of the
unit, but it can be reversed with the solid bottom panel for hori-
zontal applications.

A supply air plenum (Fig. 4), a base (Fig. 5) and a return air
grille (Fig. 6) are available as field-installed accessories, and
one of the following respective instructions will be packed with
each.

035-09651-001-A-0304

Unitary Products Group

5

FIG. 2 - VERTICAL AND HORIZONTAL APPLICATIONS

FIG. 3 - ELECTRIC HEATER ACCESSORY

(Vertical Arrangement Shown)

Plenum should be field mounted on the supply air end of indoor

units for either vertical or horizontal application. For rear discharge,

rotate plenum 180°. For horizontal discharge on a horizontal unit,

the grille panel and the top panel will be arranged differently. Refer

to Form 035-16650-001 for installation and assembly instructions.

FIG. 4 - SUPPLY AIR PLENUM ACCESSORY

(Vertical Arrangement Shown)

FIG. 5 - BASE ACCESSORY

(For Vertical Arrangement Shown)