Specifications

A–4

975-0187-01-01

Temperature Specifications

Protection Features

Nominal ambient

25 °C (77 °F)

Operating range

0 – 50 °C (32 – 122 °F)

Current de-rating

approx. 2% (Imax) / °C (50 – 65 °C) (122 – 149 °F)

Storage

-40 – 80 °C (-40 – 176 °F)

Humidity

5 – 95%, RH non-condensing

Battery reverse polarity

No damage incurred by reverse polarity.

Safe non-operating battery voltage

35 VDC maximum

Over-voltage limits

The XC Series will stop charging any bank that has a
voltage greater than + 0.5 V over the temperature
compensated absorption voltage. It will restart when
this voltage is + 0.2 V.

Output current limit

XC3012:

30 – 33 ADC

XC5012:

50 – 55 ADC

XC1524:

15 – 16.5 ADC

XC2524:

25 – 27.5 ADC

Over-temperature

Internal charger temperature is measured. Unit shuts
down and restarts as follows:

Over-temperature shutdown at 75 °C (167 °F)

Over-temperature restart at 70 °C (158 °F)

Current derating in ambient
temperatures

Rated current to 50 °C (122 °F)
2%/ °C derating above 50 °C (122 °F)

Battery over-temperature
protection

Battery temperature, as sensed by the battery
temperature sensor (if installed), results in the
charger no longer charging the individual battery or
bank at a battery temperature of 55 °C (132 °F).

XC_Charger_Owner.book Page 4 Friday, August 12, 2005 3:23 PM