York PC9*DH User Manual

Page 2

Advertising
background image

246815-YTG-D-0108

2

Unitary Products Group

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

C

19-1/4

1-1/4

1-1/4

5/8

5/8

23-5/8

D

2-1/4

23-1/4

20

B

BOTTOM IMAGE

SUPPLY END

TOP IMAGE

RETURN END

LEFT SIDE

RIGHT SIDE

22-3/4

7/8

7/8

13-7/8

HORIZONTAL CONDENSATE
DRAIN OPENING 2”

JUNCTION BOX
HOLE 7/8”

GAS PIPE ENTRY 1-1/2”

CONDENSATE DRAIN
HOLE 7/8”

SIDE PIPING HOLE 3-3/8”

T-STAT WIRING 7/8” K.O.

HORIZONTAL CONDENSATE
DRAIN OPENING 1-3/4”

22-1/4

25-3/8

26-1/2

27-1/8

29

22-3/4

21-5/8

18-1/2

11-3/4

7-1/2

2-1/4

T-STAT WIRING 7/8” K.O.

HORIZONTAL CONDENSATE
DRAIN OPENING 1-3/4”

HORIZONTAL
CONDENSATE
DRAIN OPENING 1-3/4”

JUNCTION BOX
HOLE 7/8”

GAS PIPE
ENTRY 1-1/2”

CONDENSATE DRAIN
HOLE 7/8”

29

22-3/4

21-1/4

18-1/2

9-1/8

8-1/2

30-1/8

23-11/16

E

FRONT

A

40

DIMENSIONS

Models

CFM

Cabinet

Size

Cabinet Dimension

A (in.)

B (in.)

C (in.)

D (in.)

E (IN.)

PC9B12N060DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PC9B12N080DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PC9C16N080DH11

1600

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PC9C16N100DH11

1600

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PC9C20N100DH11

2000

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PC9D20N120DH11

2000

D

24-1/2

23-1/4

22

2-1/2

3

ELECTRICAL AND PERFORMANCE DATA

Models

Input

Max/Min

Output

Max/Min

Nominal

Airflow

Cabinet Width

AFUE

Air Temp. Rise

Maximum Input

Air Temp. Rise

Minimum Input

MBH

MBH

CFM

In.

%

°F

°F

PC9B12N060DH11

60 / 21

57 / 20

1200

17-1/2

95.0

40 - 70

20 - 50

PC9B12N080DH11

80 / 28

76 / 26

1200

17-1/2

95.0

40 - 70

20 - 50

PC9C16N080DH11

80 / 28

76 / 26

1600

21

95.0

40 - 70

20 - 50

PC9C16N100DH11

100 / 35

95 / 33

1600

21

95.0

40 - 70

20 - 50

PC9C20N100DH11

100 / 35

95 / 33

2000

21

95.0

40 - 70

20 - 50

PC9D20N120DH11

120 / 42

115 / 39

2000

24-1/2

95.0

40 - 70

20 - 50

Models

Max. Outlet

Air Temp.

Blower

Blower

Size

Total

Unit

Max.

Over-current

Protect

Min. Wire Size

(awg) @ 75 ft.

One Way

Approximate

Operating

Weight

Power Supply

(Voltage-PH-Hz

°F

HP

Amps

In.

Amps

PC9B12N060DH11

170

1/2

7.7

11 x 8

9

20

14

136

115-1-60

PC9B12N080DH11

170

1/2

7.7

11 x 8

9

20

14

143

115-1-60

PC9C16N080DH11

170

3/4

9.6

11 x 10

12

20

14

159

115-1-60

PC9C16N100DH11

170

3/4

9.6

11 x 10

12

20

14

163

115-1-60

PC9C20N100DH11

170

1

12.8

11 x 11

14

20

12

165

115-1-60

PC9D20N120DH11

170

1

12.8

11 x 11

14

20

12

182

115-1-60