York PC9*DH User Manual

Page 3

Advertising
background image

246815-YTG-D-0108

Unitary Products Group

3

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

AIR FLOW DATA

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

PC9B12N060DH11

PC9B12N080DH11

JUMPER SETTINGS

CFM

CFM

High

Low

High

Low

COOL Tap

ADJ Tap

1330

900

1310

890

A

B

1130

800

1100

740

B

B

1220

850

1220

830

A

A

1040

730

1000

670

B

A

1120

770

1090

720

A

C

920

650

900

610

C

B

950

660

880

610

B

C

740

540

680

510

D

B

860

610

810

580

C

A

690

540

630

500

D

A

790

570

730

530

C

C

630

530

590

500

D

C

PC9C16N080DH11
PC9C16N100DH11

PC9C20N100DH11

JUMPER SETTINGS

CFM

CFM

High

Low

High

Low

COOL Tap

ADJ Tap

1660

1110

2210

1480

A

B

1550

1050

1780

1180

B

B

1610

1070

2040

1350

A

A

1440

960

1620

1050

B

A

1470

990

1840

1250

A

C

1370

920

1560

1010

C

B

1290

850

1470

940

B

C

1130

790

1370

890

D

B

1230

850

1460

930

C

A

1050

720

1250

790

D

A

1110

760

1310

810

C

C

950

660

1090

690

D

C

PC9D20N120DH11

JUMPER SETTINGS

CFM

High

Low

COOL Tap

ADJ Tap

2280

1510

A

B

1860

1190

B

B

2090

1370

A

A

1630

1060

B

A

1880

1250

A

C

1620

1030

C

B

1500

960

B

C

1410

880

D

B

1490

920

C

A

1290

790

D

A

1360

840

C

C

1140

690

D

C

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c.
static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static
pressure is not recommended.
NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.