HEATER / CFM LIMITATIONS

HEATER

SIZE

NOM. KW

VOLTAGE

1

UNIT MODEL SIZE, NOMINAL TONS

3

4

5

MINIMUM SUPPLY AIR CFM

5
7

10
15
20
30

208 /

230-1-60

1,100
1,100
1,200
1,200

1,300

2

-

1,300
1,300
1,300
1,300

1,300

2

-

1,600
1,600
1,600
1,600
1,600
1,600

5
7

10
15
20
30

208 /

230-3-60

1,100
1,100
1,200
1,200

1,300

2

-

1,300
1,300
1,300
1,300

1,300

2

-

1,600
1,600
1,600
1,600
1,600
1,600

HEATER

SIZE

NOM. KW

VOLTAGE

1

UNIT MODEL SIZE, NOMINAL TONS

3

4

5

MINIMUM SUPPLY AIR CFM

7

10
15
20
30

460-3-60

1,100
1,200
1,200
1,300

-

1,300
1,300
1,300
1,300

-

1,600
1,600
1,600
1,600
1,600

10
15
20
30

575-3-60

1,200
1,200
1,300

-

1,300
1,300
1.400

-

1,600
1,600
1,600
1,800

1

208/230 and 460 volt heaters are UL approved.

208/230 and 575 volt heaters are CGA approved.

2

CGA minimum is 1,400 CFM.

REFER TO ELECTRICAL DATA
TABLES TO SIZE THE
DISCONNECT SWITCH, THE
WIRING AND OVERCURRENT
PROTECTION

REFER TO ELECTRICAL DATA
TABLES TO SIZE THE
DISCONNECT SWITCH, THE
WIRING AND OVERCURRENT
PROTECTION

2

3

4

TO REMOTE SENSOR
2TH04702224 IF USED

2

1

24-volt thermostat with subbase:

—2TH11700224 for manual changeover.
—2TH11704124 for automatic changeover.

2

Only required on units with supplemental electric heat.

FIELD WIRING

CONTROL WIRING

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer

1, 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Electric Heaters

1

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

Bottom Duct Connections

1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1

Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2

The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM

during full economizer operation.

STATIC RESISTANCES