Cooling capacities, 3 ton (bch036) – York SUNLINE 2000 48 User Manual

Page 4

Advertising
background image

036-21564-002-A-0404

4

Unitary Products Group

COOLING CAPACITIES -

3 TON (BCH036)

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

85

°

F

95

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1750

72

51

3.4

37

32

28

24

19

-

-

47

3.7

34

29

25

22

17

-

-

67

46

3.4

40

40

36

31

26

21

16

44

3.7

38

38

34

29

24

20

15

62

42

3.3

42

42

41

39

34

29

24

38

3.6

38

38

37

35

30

26

21

57

42

3.3

42

42

42

40

35

30

25

37

3.6

37

37

37

35

30

26

22

1500

72

49

3.4

35

30

26

22

18

-

-

46

3.7

32

28

24

20

16

-

-

67

45

3.4

39

37

33

29

24

20

15

42

3.7

36

34

30

27

22

18

14

62

41

3.3

41

41

40

37

32

28

24

37

3.6

37

37

36

33

28

25

21

57

41

3.3

41

41

41

38

34

29

25

36

3.6

36

36

36

33

29

25

21

1400

72

48

3.4

33

29

24

20

16

-

-

45

3.7

30

27

22

18

15

-

-

67

44

3.3

39

36

32

28

23

20

15

41

3.7

36

33

29

26

21

18

13

62

40

3.3

40

39

38

34

30

26

22

36

3.6

36

35

34

30

27

23

19

57

40

3.3

40

40

39

35

31

27

23

36

3.5

36

36

35

31

27

24

20

1200

72

47

3.4

31

27

24

20

16

-

-

44

3.7

29

25

22

18

14

-

-

67

41

3.3

36

32

29

25

22

18

14

39

3.6

34

30

27

23

20

17

13

62

38

3.3

38

37

36

32

29

25

21

35

3.6

35

34

33

29

26

23

19

57

37

3.3

37

37

36

33

30

26

22

35

3.5

35

35

34

31

28

24

20

1050

72

45

3.3

28

25

22

19

16

-

-

42

3.6

26

23

20

17

14

-

-

67

41

3.3

34

30

27

24

20

17

14

38

3.6

31

27

25

22

18

15

12

62

36

3.3

36

35

33

30

27

24

21

34

3.5

34

33

31

28

25

22

19

57

36

3.3

36

36

34

31

28

25

22

33

3.5

33

33

31

28

25

22

20

900

72

45

3.3

26

24

20

17

15

-

-

40

3.6

23

21

17

15

13

-

-

67

39

3.3

31

28

25

22

19

17

14

35

3.6

27

25

22

19

17

15

12

62

35

3.2

35

34

32

29

25

23

20

32

3.5

32

30

28

25

22

20

17

57

35

3.2

35

35

32

30

26

24

21

31

3.5

31

31

28

26

23

21

18

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

105

°

F

115

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1750

72

44

4.0

31

27

24

20

16

-

-

42

4.2

30

26

23

19

15

-

-

67

40

4.0

34

34

31

26

22

18

13

36

4.1

31

31

28

24

20

16

12

62

35

3.9

35

35

34

32

28

24

20

34

4.1

34

34

33

31

27

23

19

57

35

3.9

35

35

35

33

29

25

20

33

4.1

33

33

33

31

27

23

19

1500

72

43

4.0

30

26

22

19

15

-

-

41

4.2

29

25

21

18

15

-

-

67

38

4.0

32

31

27

24

20

16

12

35

4.1

30

28

25

22

18

15

11

62

34

3.9

34

34

33

30

26

23

19

33

4.1

33

33

32

29

25

22

19

57

34

3.9

34

34

34

31

28

24

20

32

4.1

32

32

32

29

26

22

19

1400

72

42

4.0

28

25

21

17

14

-

-

39

4.2

26

23

19

16

13

-

-

67

37

4.0

32

30

26

23

19

16

12

34

4.1

30

27

24

21

17

15

11

62

33

3.9

33

32

31

28

24

21

18

32

4.1

32

31

30

27

24

20

17

57

32

3.8

32

32

31

28

24

21

18

32

4.0

32

32

31

28

24

21

18

1200

72

41

4.0

27

23

20

17

13

-

-

37

4.2

24

21

18

15

12

-

-

67

35

3.9

30

27

24

21

18

15

11

32

4.1

28

24

22

19

17

14

10

62

32

3.9

32

31

30

26

24

21

17

30

4.1

30

29

28

25

22

19

16

57

31

3.8

31

31

31

27

25

21

18

29

4.0

29

29

29

25

23

20

17

1050

72

40

3.9

24

22

19

16

14

-

-

35

4.1

21

19

17

14

12

-

-

67

34

3.9

28

24

22

19

16

14

11

31

4.0

25

22

20

18

15

12

10

62

30

3.8

30

29

27

25

22

20

17

29

4.0

29

28

26

24

21

19

16

57

30

3.8

30

30

28

25

23

20

18

28

4.0

28

28

26

24

21

19

17

900

72

38

3.9

21

20

16

14

12

-

-

34

4.1

19

18

15

12

11

-

-

67

32

3.9

25

22

20

18

15

13

11

29

4.0

23

20

18

16

14

12

10

62

29

3.8

29

27

25

23

20

18

16

27

4.0

27

25

24

21

18

17

15

57

29

3.8

29

29

26

24

21

19

17

26

4.0

26

26

23

22

19

17

15

1

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by

3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2

These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.

Refer to the Blower Performance Table for the KW of the supply air blower motor.

ALL SENSIBLE CAPACITY

NOMINAL RATING

Advertising
This manual is related to the following products: