COOLING CAPACITIES -

4 TON (BCH048)

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

85

°

F

95

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

2000

72

56

4.1

42

36

31

26

-

-

-

53

4.5

40

35

29

24

-

-

-

67

53

4.0

48

47

41

36

30

25

-

51

4.4

46

45

41

35

30

24

-

62

49

4.0

49

49

48

44

38

33

28

46

4.3

46

46

45

41

35

30

24

57

49

3.9

49

49

49

44

38

33

28

46

4.3

46

46

46

41

35

30

24

1800

72

55

4.0

40

35

30

25

-

-

-

53

4.4

38

33

28

23

-

-

-

67

52

4.0

47

44

39

34

29

24

-

51

4.4

44

44

39

34

29

24

-

62

48

3.9

48

48

47

43

38

33

28

47

4.3

47

47

45

40

36

31

26

57

48

3.9

48

48

48

43

38

33

28

45

4.2

45

45

45

40

35

30

25

1600

72

53

4.0

37

33

28

24

-

-

-

52

4.4

36

32

27

23

-

-

-

67

51

4.0

46

42

37

33

28

24

-

50

4.3

44

43

38

34

29

25

-

62

47

3.9

47

47

46

41

37

32

28

45

4.2

45

45

44

40

36

31

27

57

47

3.9

47

47

47

42

38

33

29

44

4.1

44

44

44

40

36

31

27

1400

72

52

4.0

34

30

26

22

-

-

-

49

4.3

33

29

25

21

-

-

-

67

49

3.9

42

38

34

30

26

22

-

47

4.2

42

38

34

30

26

22

-

62

46

3.8

46

45

42

38

34

30

26

43

4.1

43

42

40

36

32

28

24

57

45

3.8

45

45

43

39

35

31

27

42

4.1

42

42

40

36

32

28

24

1200

72

50

3.9

31

27

24

20

-

-

-

47

4.2

29

25

22

18

-

-

-

67

47

3.9

38

35

31

28

24

21

-

45

4.2

37

34

30

27

23

20

-

62

44

3.8

44

42

39

35

32

28

25

40

4.1

40

39

36

32

29

25

22

57

44

3.7

44

43

39

36

32

29

25

40

4.0

40

39

36

32

29

25

22

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

105

°

F

115

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

2000

72

51

4.9

40

35

29

24

-

-

-

49

5.2

39

34

29

23

-

-

-

67

46

4.7

42

42

39

34

28

23

-

41

5.0

40

40

37

32

26

21

-

62

43

4.6

43

43

42

37

32

27

21

40

4.9

40

40

39

34

29

23

18

57

43

4.6

43

43

43

38

32

28

22

40

4.8

40

40

40

34

30

24

19

1800

72

50

4.8

38

33

28

23

-

-

-

47

5.1

37

32

27

22

-

-

-

67

45

4.7

41

41

37

32

27

22

-

40

4.9

37

36

35

30

25

20

-

62

42

4.6

42

42

41

37

32

27

22

39

4.8

39

39

37

34

29

24

19

57

42

4.5

42

42

42

37

33

27

23

38

4.7

38

38

38

33

30

25

20

1600

72

49

4.8

35

31

26

22

-

-

-

46

5.1

34

29

25

20

-

-

-

67

44

4.6

40

40

35

31

26

22

-

39

4.9

36

36

32

28

23

19

-

62

41

4.5

41

41

40

35

32

27

23

37

4.7

37

37

36

33

28

24

19

57

41

4.4

41

41

41

36

32

28

23

37

4.7

37

37

37

34

28

25

20

1400

72

47

4.7

32

28

24

20

-

-

-

44

5.0

31

27

23

19

-

-

-

67

42

4.5

38

36

32

28

24

20

-

37

4.8

36

34

30

26

21

17

-

62

39

4.4

39

38

37

33

28

25

20

36

4.7

36

35

34

30

26

22

18

57

39

4.4

39

39

37

33

29

25

21

36

4.6

36

36

34

31

26

23

19

1200

72

44

4.6

28

25

21

18

-

-

-

42

4.9

28

24

21

17

-

-

-

67

40

4.5

36

32

29

25

22

18

-

36

4.7

34

31

27

24

20

17

-

62

38

4.4

38

36

34

29

27

22

20

35

4.6

35

34

30

28

24

20

17

57

37

4.3

37

37

34

30

27

23

20

35

4.6

35

35

31

29

24

21

18

1

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by

3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2

These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.

Refer to the Blower Performance Table for the KW of the supply air blower motor.

ALL SENSIBLE CAPACITY

NOMINAL RATING