COOLING CAPACITY - With Air Handler Coils

UNIT

MODEL

AIR HANDLER

COIL

MODEL

1

STAGE

COOLING

MODEL

W

RATED

CFM

NET MBH

SEER

EER

TOTAL

SENS.

14.5 SEER HP WITH MV - VARIABLE SPEED

YHJF18S41S1

MV12B

17

FC/MC35B

600

18.0

13.0

15.00

12.50

MV12B

17

FC/MC43B

600

18.0

13.3

15.00

12.50

YHJF24S41S1

MV12B

17

FC/MC35B

800

22.8

17.2

15.00

12.50

MV12B

17

FC/MC43B

800

23.4

18.0

15.00

12.50

YHJF30S41S1

MV12B

17

FC/MC43B

1000

29.0

21.6

15.00

12.50

MV16C

21

FC/MC43C

1000

29.0

21.6

15.00

12.50

YHJF36S41S1

MV12B

17

FC/MC43B

1225

35.4

26.6

14.35

12.00

MV16C

21

FC/MC43C

1200

35.2

26.4

14.50

12.00

YHJF42S41S1

MV20D

24

FC/MC62D

1400

40.0

30.8

14.50

12.00

YHJF48S41S1

MV20D

24

FC/MC62D

1630

48.0

36.2

15.00

12.50

YHJF60S41S1

MV20D

24

FC/MC62D

1

1160

48.0

31.0

14.50

12.00

2

1855

57.0

40.5

14.5 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED

YHJF18S41S1

AV*36

21

630

18.0

13.3

15.00

12.50

YHJF24S41S1

AV*36

21

725

22.8

16.8

15.00

12.50

YHJF30S41S1

AV*36

21

960

29.2

21.8

15.00

12.50

YHJF36S41S1

AV*36

21

1190

35.4

26.4

14.50

12.00

14.5 SEER HP WITH AHP / SHP / AHX / F*FP

YHJF18S41S1

AHX30

17

640

18.0

13.3

15.00

12.50

YHJF24S41S1

AHX30

17

800

22.8

17.1

15.00

12.50

F6FP030

17

850

22.8

17.3

14.50

12.00

F6FP036

21

855

22.8

17.4

15.00

12.50

AHX36

21

820

23.0

17.4

15.00

12.50

YHJF30S41S1

AHX36

21

1030

29.4

22.2

15.00

12.50

F6FP042

21

1065

29.4

22.2

15.00

12.50

YHJF36S41S1

AHX36

21

1210

35.4

26.6

14.50

12.00

AHX42

21

1190

35.8

26.8

15.00

12.50

F6FP042

24

1290

36.0

27.6

15.00

12.50

YHJF42S41S1

AHX60

24

1355

40.0

30.2

14.50

12.00

F6FP060

24

1475

40.5

31.4

14.50

12.00

YHJF48S41S1

AHX60

24

1570

48.0

35.6

15.00

12.50

F6FP060

24

1570

48.0

35.6

15.00

12.50

YHJF60S41S1

AHX60

24

1

1160

47.5

30.5

14.50

12.00

2

1855

57.0

40.5

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8

°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.

1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

Advertising