York E4TS030 THRU 060 User Manual

Page 12

Advertising
background image

036-21342-002 Rev. E (0505)

12

Unitary Products Group

ACCESSORIES

Refer to Price Manual for specific model numbers.

TXV Kit - Factory specified and required for proper unit per-
formance.

E4TS030 = 1TV0701
E4TS036 = 1TV0702
E4TS048 = 1TV0703
E4TS060 = 1TV0703

Room Thermostat - Matching 2-Stage cooling thermostats
are available to provide features required for any installation.
See list below:

2ET03700624 - Honeywell Programmable
2ET03700524 - Honeywell Non-Programmable
2EP32U70124 - White Rodgers Programmable

Dehumidification Control - Model 2HU06700124 available
for use in areas where a higher level of humidity control is
required.

Fossil Fuel Relay (Model 2FF02700101) - Required for use
with all furnace applications.

SOUND RATINGS*

* Rated in accordance with ARI 270-95 Standards.

E4TS048

P1XDD20V112

G2FD060S24

1

880

21400

-

-

3.30

2

880

43000

23800

7.7

3.34

2

1580

46500

25800

8.0

3.52

G2FD061H24

1

880

22000

-

-

3.38

2

880

44000

24400

7.9

3.42

2

1580

47500

26400

8.2

3.60

P1XUD20V112

24

G1UA060S24

1

915

22200

-

-

3.34

2

915

44000

25000

7.8

3.36

2

1620

47500

27000

8.1

3.54

G1FA060S24

1

915

22200

-

-

3.34

2

915

44000

25000

7.8

3.36

2

1620

47500

27000

8.1

3.54

G2FD060S24

1

915

22200

-

-

3.34

2

915

44000

25000

7.8

3.36

2

1620

47500

27000

8.1

3.54

G2FD061H24

1

915

22600

-

-

3.40

2

915

45000

25600

8.0

3.44

2

1620

48500

27600

8.3

3.62

E4TS060

P1XDD20V112

G2FD060S24

1

1000

23400

-

-

3.38

2

1000

49500

26000

7.5

3.28

2

1800

54000

28400

7.9

3.46

G2FD061H24

1

1000

23400

-

-

3.48

2

1000

50500

26600

7.9

3.35

2

1800

55000

29000

8.2

3.52

P1XUD20V112

24

G1UA060S24

1

990

23200

-

-

3.34

2

990

49500

26000

7.6

3.34

2

1800

54000

28400

8.0

3.52

G1FA060S24

1

990

23200

-

-

3.34

2

990

49500

26000

7.6

3.34

2

1800

54000

28400

8.0

3.52

G2FD060S24

1

990

23200

-

-

3.34

2

990

49500

26000

7.6

3.34

2

1800

54000

28400

8.0

3.52

G2FD061H24

1

990

23200

-

-

3.42

2

990

50500

26600

8.0

3.40

2

1800

55000

29000

8.3

3.58

1. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and

no supplemental electric heat operation.

2. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
3. HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided

by the total electric power input during the same period.

4. COP equals MBH output divided by (total KW input x 3.412).

HEATING CAPACITY - Variable Speed Furnace (Continued)

UNIT

MODEL

VARIABLE SPEED

FURNACE MODEL

W

COIL MODEL

HEATING

STAGE

(# CYL)

RATED

CFM

NET MBH

1,2

HSPF

3

COP

4

@ 47 F

47 OD

17 OD

UNIT MODEL

SOUND RATINGS

(dba)

1 CYLINDER

2 CYLINDER

030

72

73

036

75

78

048

77

79

060

79

81

Advertising