York SUNLINE 2000 BP 072 User Manual

Page 16

Advertising
background image

036-21630-001-B-0904

16

Unitary Products Group

TABLE 3: BP072 COOLING CAPACITIES (6 TON)

RETURN AIR

OUTDOOR AMBIENT TEMPERATURE

85°F

95°F

GROSS

CAP.

1

MBH

INPUT

2

POWER

kW

GROSS SENSIBLE CAPACITY

1

, MBH

GROSS

CAP.

1

MBH

INPUT

2

POWER

kW

GROSS SENSIBLE CAPACITY

1

, MBH

RETURN AIR DRY BULB TEMP. °F

RETURN AIR DRY BULB TEMP. °F

CFM

WB

TEMP

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1800

72

76.1

5.26

45.5 39.7 33.8 28.0 22.2 -

-

72.6

5.80

43.1 38.0 32.9 27.7 22.6 -

-

67

71.2

5.19

57.8 51.9 46.1 40.3 34.4 28.6 22.8

67.0

5.74

55.0 49.9 44.7 39.6 34.5 29.3 24.2

62

66.0

5.13

66.0 62.8 57.0 51.2 45.3 39.5 33.7

60.9

5.67

60.9 59.8 54.7 49.5 44.4 39.3 34.1

57

65.4

5.12

65.4 64.0 58.1 52.3 46.5 40.6 34.8

60.7

5.67

60.7 59.9 54.7 49.6 44.5 39.3 34.2

2100

72

78.9

5.28

49.9 43.4 37.0 30.6 24.2 -

-

75.7

5.83

48.2 42.1 36.0 30.0 23.9 -

-

67

73.8

5.21

63.3 56.9 50.4 44.0 37.6 31.2 24.8

69.8

5.77

61.2 55.1 49.0 43.0 36.9 30.8 24.8

62

68.3

5.15

68.3 66.8 62.4 56.0 49.6 43.1 36.7

63.4

5.70

63.4 62.9 59.9 53.9 47.8 41.7 35.7

57

67.8

5.14

67.8 67.0 63.6 57.2 50.8 44.4 38.0

63.2

5.70

63.2 62.8 60.0 53.9 47.9 41.8 35.7

2400

72

81.6

5.30

54.2 47.2 40.2 33.2 26.2 -

-

78.7

5.86

53.2 46.2 39.2 32.2 25.2 -

-

67

76.3

5.23

68.8 61.8 54.8 47.8 40.8 33.8 26.8

72.6

5.80

67.3 60.3 53.3 46.3 39.4 32.4 25.4

62

70.7

5.17

70.7 70.7 67.8 60.8 53.8 46.8 39.8

66.0

5.73

66.0 66.0 65.2 58.2 51.2 44.2 37.2

57

70.1

5.16

70.1 70.1 69.1 62.1 55.1 48.1 41.1

65.7

5.72

65.7 65.7 65.3 58.3 51.3 44.3 37.3

2700

72

83.3

5.31

58.0 50.1 42.1 34.1 26.2 -

-

79.6

5.87

56.9 48.9 41.0 33.0 25.0 -

-

67

77.9

5.24

73.3 65.3 57.4 49.4 41.4 33.5 25.5

73.4

5.81

70.8 63.7 55.8 47.8 39.8 31.9 23.9

62

72.1

5.18

72.1 72.1 70.7 62.7 54.7 46.8 38.8

66.7

5.74

66.7 66.7 66.3 58.4 50.4 42.4 34.4

57

71.6

5.17

71.6 71.6 71.1 63.1 55.1 47.2 39.2

66.5

5.74

66.5 66.5 66.3 58.3 50.3 42.3 34.4

3000

72

84.9

5.32

61.9 52.9 44.0 35.0 26.1 -

-

80.5

5.89

60.6 51.7 42.8 33.8 24.9 -

-

67

79.5

5.25

77.8 68.9 59.9 51.0 42.0 33.1 24.2

74.2

5.83

74.2 67.1 58.2 49.3 40.3 31.4 22.4

62

73.6

5.19

73.6 73.6 73.6 64.7 55.7 46.8 37.8

67.5

5.76

67.5 67.5 67.5 58.5 49.6 40.6 31.7

57

73.0

5.18

73.0 73.0 73.0 64.1 55.1 46.2 37.2

67.2

5.76

67.2 67.2 67.2 58.3 49.4 40.4 31.5

RETURN AIR

OUTDOOR AMBIENT TEMPERATURE

105°F

115°F

GROSS

CAP.

1

MBH

INPUT

2

POWER

kW

GROSS SENSIBLE CAPACITY

1

, MBH

GROSS

CAP.

1

MBH

INPUT

2

POWER

kW

GROSS SENSIBLE CAPACITY

1

, MBH

RETURN AIR DRY BULB TEMP. °F

RETURN AIR DRY BULB TEMP. °F

CFM

WB

TEMP

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1800

72

67.5

6.47

40.8 35.7 30.6 25.5 20.3 -

-

62.3

7.14

38.6 33.4 28.3 23.2 18.0 -

-

67

61.4

6.38

52.1 46.9 41.8 36.7 31.5 26.4 21.3

55.8

7.02

49.2 44.0 38.9 33.8 28.6 23.5 18.4

62

56.3

6.33

56.3 55.4 50.3 45.1 40.0 34.9 29.7

51.8

6.98

51.8 51.0 45.9 40.7 35.6 30.5 25.3

57

55.9

6.31

55.9 55.0 49.9 44.8 39.6 34.5 29.4

51.1

6.95

51.1 50.2 45.0 39.9 34.8 29.6 24.5

2100

72

70.8

6.51

46.1 40.1 34.0 27.9 21.9 -

-

66.0

7.19

44.1 38.0 32.0 25.9 19.8 -

-

67

64.4

6.41

58.5 52.6 46.5 40.4 34.4 28.3 22.2

59.1

7.06

55.7 50.0 43.9 37.9 31.8 25.7 19.7

62

59.1

6.36

59.1 58.7 55.9 49.8 43.7 37.7 31.6

54.8

7.03

54.8 54.4 51.8 45.7 39.7 33.6 27.5

57

58.6

6.34

58.6 58.2 55.4 49.4 43.3 37.3 31.2

54.0

6.99

54.0 53.6 50.9 44.8 38.8 32.7 26.6

2400

72

74.2

6.55

51.4 44.4 37.4 30.4 23.4 -

-

69.6

7.23

49.6 42.6 35.6 28.6 21.6 -

-

67

67.4

6.45

64.8 58.2 51.2 44.2 37.2 30.2 23.2

62.3

7.11

62.3 56.0 49.0 42.0 35.0 28.0 21.0

62

61.9

6.40

61.9 61.9 61.5 54.5 47.5 40.5 33.5

57.9

7.07

57.9 57.9 57.8 50.8 43.8 36.8 29.8

57

61.4

6.38

61.4 61.4 61.0 54.0 47.0 40.0 33.0

57.0

7.04

57.0 57.0 56.7 49.7 42.7 35.7 28.7

2700

72

74.3

6.56

54.7 46.8 38.8 30.8 22.8 -

-

69.1

7.25

52.5 44.6 36.6 28.6 20.7 -

-

67

67.6

6.47

66.3 61.0 53.0 45.1 37.1 29.1 21.2

61.8

7.13

61.8 58.3 50.3 42.3 34.4 26.4 18.4

62

62.1

6.42

62.1 62.1 61.9 53.9 45.9 37.9 30.0

57.4

7.09

57.4 57.4 57.4 49.4 41.4 33.5 25.5

57

61.5

6.40

61.5 61.5 61.3 53.4 45.4 37.4 29.5

56.6

7.06

56.6 56.6 56.4 48.5 40.5 32.5 24.6

3000

72

74.5

6.58

58.0 49.1 40.2 31.2 22.3 -

-

68.6

7.27

55.4 46.5 37.6 28.6 19.7 -

-

67

67.8

6.49

67.8 63.9 54.9 46.0 37.0 28.1 19.1

61.4

7.15

61.4 60.6 51.6 42.7 33.7 24.8 15.8

62

62.2

6.44

62.2 62.2 62.2 53.3 44.3 35.4 26.5

57.0

7.11

57.0 57.0 57.0 48.1 39.1 30.2 21.2

57

61.7

6.42

61.7 61.7 61.7 52.8 43.8 34.9 25.9

56.1

7.08

56.1 56.1 56.1 47.2 38.3 29.3 20.4

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 X kW. Refer to the

appropriate blower performance table for the KW of the supply air blower motor.

2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

Advertising