York SUNLINE 2000 BP 072 User Manual

Page 17

Advertising
background image

036-21630-001-B-0904

Unitary Products Group

17

TABLE 3: BP072 COOLING CAPACITIES (6 TON) - CONTINUED

RETURN AIR

OUTDOOR AMBIENT TEMPERATURE

125°F

GROSS

CAP.

1

MBH

INPUT

2

POWER

kW

GROSS SENSIBLE CAPACITY

1

, MBH

RETURN AIR DRY BULB TEMP. °F

CFM

WB

TEMP

°F

86

83

80

77

74

71

68

1800

72

57.2

7.81

36.3 31.2 26.0 20.9 15.8 -

-

67

50.2

7.66

46.2 41.1 36.0 30.8 25.7 20.6 15.4

62

47.3

7.64

47.3 46.6 41.5 36.3 31.2 26.1 20.9

57

46.2

7.59

46.2 45.3 40.2 35.1 29.9 24.8 19.7

2100

72

61.1

7.87

42.1 36.0 29.9 23.9 17.8 -

-

67

53.7

7.71

53.0 47.5 41.4 35.3 29.3 23.2 17.1

62

50.6

7.69

50.6 50.2 47.8 41.7 35.6 29.6 23.5

57

49.5

7.64

49.5 49.0 46.3 40.3 34.2 28.1 22.1

2400

72

65.1

7.92

47.9 40.9 33.9 26.9 19.9 -

-

67

57.2

7.76

57.2 53.8 46.8 39.8 32.8 25.8 18.8

62

53.8

7.75

53.8 53.8 53.8 47.0 40.0 33.1 26.1

57

52.7

7.70

52.7 52.7 52.5 45.5 38.5 31.5 24.5

2700

72

63.8

7.94

50.4 42.4 34.4 26.4 18.5 -

-

67

56.1

7.79

56.1 55.5 47.6 39.6 31.6 23.6 15.7

62

52.8

7.77

52.8 52.8 52.8 44.9 37.0 29.0 21.0

57

51.6

7.72

51.6 51.6 51.5 43.6 35.6 27.6 19.6

3000

72

62.6

7.97

52.8 43.9 35.0 26.0 17.1 -

-

67

54.9

7.81

54.9 54.9 48.3 39.4 30.4 21.5 12.6

62

51.8

7.79

51.8 51.8 51.8 42.8 33.9 24.9 16.0

57

50.6

7.74

50.6 50.6 50.6 41.7 32.7 23.8 14.8

1. These capacities are gross ratings. For net capacity, deduct the

supply air blower motor heat, MBH = 3.415 X kW. Refer to the
appropriate blower performance table for the KW of the supply air
blower motor.

2. These ratings include condenser fan motor and compressor motor

power but not the supply air blower motor power.