Table 6: belt drive blower motor and drive data – York SUNLINE 2000 BP 072 User Manual

Page 19

Advertising
background image

036-21630-001-B-0904

Unitary Products Group

19

TABLE 6: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

MODEL

SIZE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP

FRAME

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

6 TON

900/1250

1 1/2

56

1VL44

3.1-4.1

2.8-3.8

7/8

AK56

5.4

5.2

1

A36

37.3

1

1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located

in the moving air, upstream of any heating device.

TABLE 7: STATIC RESISTANCES

TABLE 8: ELECTRIC HEATER CFM LIMITATIONS

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

COOLING ONLY

2

RESISTANCE, IWG

CFM

DESCRIPTION

ECONOMIZER

1 3

BOTTOM DUCT CONNECTIONS

1

ELECTRIC

HEATERS

1

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

5

7

10

15

20

30

208/230-1-60

1800

1800

1800

1800

1800

1800

208/230-3-60

1800

1800

1800

1800

1800

1800

460-3-60

-

1800

1800

1800

1800

1800

575-3-60

-

-

1800

1800

1800

1800

6

MINIMUM SUPPLY AIR CFM

HEATER SIZE NOMINAL KW

VOLTAGE

UNIT MODEL SIZE NOMINAL

TONS

Advertising