Installation - ductwork calculation sheet – Zephyr ZVE-E42S User Manual

Page 6

Advertising
background image

www.zephyronline.com

4

Installation

-

Ductwork

Calculation

Sheet

Duct pieces

Total

Equivalent number
length x used =

3 1/4” x 10”
Rect.,
straight

1 Ft. x ( ) =

Ft.

7” Round,
straight

1 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect. 90

0

elbow

15 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect. 45

0

elbow

9 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect. 90

0

flat elbow

24 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect.
wall cap
with damper

30 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect. to
6” round
transition

5 Ft. x ( ) =

Ft.

3 1/4” x 10”
Rect. to
6” round
transition
90

0

elbow

15 Ft. x ( ) =

Ft.

6” Round,
90

0

elbow

15 Ft. x ( ) =

Ft.

6” Round,
45

0

elbow

9 Ft. x ( ) =

Ft.

Ft.

7” Round,
straight

1 Ft. x ( ) =

Ft.

Subtotal column 1 =

Duct pieces

Total

Equivalent number
length x used =

6” Round
wall cap
with damper

30 Ft. x ( ) =

Ft.

7” Round
wall cap
with damper

30 Ft. x ( ) =

Ft.

7” Round,
90

0

elbow

15 Ft. x ( ) =

Ft.

7” Round,
45

0

elbow

9 Ft. x ( ) =

Ft.

Ft.

Ft.

Ft.

6” Round,
roof cap

30 Ft. x ( ) =

Ft.

7” Round,
roof cap

30 Ft. x ( ) =

Ft.

Subtotal column 2 =

Subtotal column 1 =

Total ductwork =

Maximum Duct Length:

For satisfactory air movement,

the total duct length of a 3 1/4” x 10” rectangular, 6” or 7”
diameter round ductshould not exceed 100 equivalent feet.

6” round to
3 1/4” x 10”
rect.
transition

1 Ft. x ( ) =

Ft.

6” round to
3 1/4” x 10”
rect.
transition
90

0

elbow

16 Ft. x ( ) =

Ft.

7” round to
3 1/4” x 10”
rect.
transition

8 Ft. x ( ) =

Ft.

7” round to
3 1/4” x 10”
rect.
transition
90

0

elbow

15 Ft. x ( ) =

Ft.