York HC User Manual

Page 5

Advertising
background image

331471-YTG-A-0507

Unitary Products Group

5

COOLING CAPACITY - COIL ONLY

*

Model Coil

Rated CFM

Entering Air °F (Wet Bulb)

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

uncased upflow

UC18A
UC18B

600

72

23.3

21.3

19.0

17.5

67

21.5

19.5

17.3

14.9

62

17.7

15.6

13.5

11.4

57

14.4

12.4

10.4

8.0

UC24A
UC24B

800

72

27.4

25.0

22.3

19.4

67

25.3

22.9

20.3

17.5

62

20.8

18.4

15.9

13.4

57

16.9

14.6

12.2

9.4

UC30A
UC30B

1000

72

35.2

32.0

28.6

24.8

67

32.4

28.6

25.3

21.9

62

26.6

23.6

21.5

18.7

57

25.2

22.7

20.2

17.6

UC36A

1150

72

46.8

42.7

37.9

33.0

67

43.1

39.2

34.9

30.4

62

35.3

32.1

28.6

24.9

57

33.3

26.9

26.9

23.4

UC36B
UC36C

1200

72

49.3

44.9

39.9

34.7

67

45.4

41.3

36.7

32.0

62

37.2

33.8

30.1

26.2

57

35.0

28.3

28.3

24.6

UC42B
UC42C

1400

72

86.7

73.0

59.2

44.9

67

69.4

57.2

45.2

33.1

62

54.0

42.3

33.4

26.8

57

46.4

40.0

33.4

26.8

UC48C
UC48D

1600

72

62.4

56.8

50.5

44.4

67

57.4

53.2

46.5

40.5

62

47.1

42.8

38.1

33.2

57

44.3

40.3

35.8

31.2

UC60C
UC60D

1800

72

95.4

82.1

68.4

54.0

67

76.4

64.1

52.2

39.9

62

59.6

47.4

38.6

32.4

57

51.2

44.8

38.6

32.4

* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

COOLING CAPACITY - COIL ONLY

*

Model Coil

Rated CFM

Entering Air °F (Wet Bulb)

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

Uncased Upflow/Downflow

MH30S

1000

72

41.5

37.8

33.7

29.5

67

36.2

32.4

28.6

24.5

62

29.1

25.3

24.0

19.2

57

24.1

21.5

18.7

15.8

MH36S

1200

72

53.4

48.6

43.4

38.3

67

42.8

37.8

33.1

28.2

62

33.4

28.1

30.6

22.8

57

28.7

26.5

24.5

22.8

MH42S

1400

72

88.4

76.0

63.3

50.0

67

70.8

59.4

48.4

37.0

62

55.2

43.9

35.8

29.9

57

47.4

41.5

35.8

29.9

* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.