Installing the inverter

975-0128-01-01

3–11

AC Connections

You can plug your AC loads directly into the receptacles on the inverter

front panel. Output power to each receptacle is limited by a circuit

breaker to 1500 Watts (15 A).
You may also make a permanent AC connection via the AC knockout.

This connection must be made in accordance with applicable electrical

codes. If you are not familiar with the applicable electrical codes and

wiring practices, we recommend you have the inverter installed by a

qualified electrician.

Connecting the Chassis Ground

The inverter has a lug connector labelled

CHASSIS GND

on the rear panel

as shown in Figure 3-4. This lug is used to connect the chassis of the

inverter to your system’s DC grounding point as required by regulations

for some installations. Follow the guidelines in “Grounding Locations” to

connect the inverter’s chassis to the ground.
Use copper wire that is provided with green insulation. Do not use the DC

Ground Lug for your AC grounding.