Xantrex Technology 3000 User Manual

Page 43

Advertising
background image

Troubleshooting Reference

975-0128-01-01

5–3

Consumer Hotline: 1-800-670-0707

5

E03

: Flashing

Fault

LED

: Flashing

Alarm: Beeping

Inverter is in
overload shutdown.

Load applied is above
the continuous operation
limit.

Reduce the load if continuous
operation is required.

6

E04

: Flashing

Fault

LED

: Flashing

Alarm: Beeping

Inverter is in
thermal shutdown.

AL2

warning code is

ignored. (See possible
causes under error # “2”
in this table).

See solution under error # “2”
in this table.

7

E05

: Flashing

Fault

LED

: Flashing

Alarm: Beeping

Output on inverter
is shortcircuit

N/A

Remove the short circuit.

8

N/A

Low output voltage
(96 VAC–104 VAC)

You are using a
voltmeter that cannot
accurately read the RMS
voltage of a modified
sine wave.

Use a true RMS reading
voltmeter such as the Fluke
87.

9

N/A

Low output voltage
on a true RMS
reading voltmeter.

Low input voltage and
the load is close to
maximum allowable
power.

Check the connections and
cable to see if the battery is
fully charged. Recharge the
battery if it is low.

Reduce the load.

10 N/A

No output voltage;
no input voltage
indication.

The inverter is off.

No power to the inverter.

Inverter fuse open.

The inverter could have
been connected with
reverse DC input
polarity.

Battery disconnect
switch or breaker is off.

Turn the inverter on.

Check the wiring to the
inverter.

Return the inverter.

The inverter has probably
been damaged. Have it
repaired. Damage caused by
reverse polarity is not covered
by the warranty.

Close battery disconnect
switch or breaker.

Table 5-1

Troubleshooting Reference

#

Error/Warning
Code on Display

Problem

Possible Cause

Solution