York AVY24 THRU 60 User Manual

Page 5

Advertising
background image

Johnson Controls Unitary Products

5

256819-YTG-J-1208

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow

80%

90%

Rated CFM

110%

120%

Capacity Factor

0.96

0.98

1.00

1.02

1.03

PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models

AVY24B**H21

AVY36C**H21

AVY48D**H21
SVY48D**N21

AVY60D**H21
SVY60D**N21

Blower - Diameter x Width

10 x 7

10 x 7

10 x 10

10 x 10

Motor

HP

1/3

1/2

3/4

1

Nominal RPM

1200

1200

1200

1200

Voltage

230

Amps

Full Load (230)

2.8

4.3

5.5

7.0

Filter

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x1

20 x 20 x1

22 x 20 x1

22 x 20 x1

Permanent Type Kit

1PF0601BK

1PF0602BK

1PF0603BK

1PF0603BK

Shipping / Operating Weight (lbs.)

140/134

170/164

AV - 196/185

SV - 194/181

AV - 199/188

SV - 195/184

1.Field supplied.

ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P.

Amps/Type

1

Minimum Wire

Size A.W.G.

60 Hertz

60 Hertz

208V

230V

208V

230V

AVY24B**H21

3.2

2.8

4.0

3.5

15

14

AVY36C**H21

4.7

4.3

5.9

5.4

15

14

AVY48D**H21

6.1

5.0

7.6

6.9

15

14

SVY48D**N21

6.1

5.0

7.6

6.9

15

14

AVY60D**H21

7.8

7.0

9.7

8.8

15

14

SVY60D**N21

7.8

7.0

9.7

8.8

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.