ELECTRICAL DATA - 208/230-3-60

Models

Heat Kit -

Three Phase

Max.

Static

Min.

Speed

Tap

Total Heat

1

KW Staging

KW

MBH

W1 Only

W2 Only

W1 + W2

208V

230V

208V

230V

208V

230V

208V

230V

208V

230V

AVY24B**H21

4HK06501025

0.5

Heat-B

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

AVY36C**H21

4HK06501025

0.5

Heat-C

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK06501525

0.5

Heat-C

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

AVY48D**H21

SVY48D**N21

4HK06501025

0.5

Heat-C

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK06501525

0.5

Heat-C

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

4HK06501825

0.5

Heat-B

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

AVY60D**H21

SVY60D**N21

4HK06501025

0.5

Heat-C

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK06501525

0.5

Heat-C

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

4HK16502525

0.5

Heat-C

18.0

24.0

61.4

81.4

9.0

12.0

18.0

24.0

18.0

24.0

1. See conversion table on Page 5.

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

Models

Heat Kit -

Three Phase

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

208V

230V

208V

230V

208V

230V

AVY24B**H21

4HK06501025

23.1

28.5

32.4

30

35

10

8

AVY36C**H21

4HK06501025

23.1

30.4

34.3

30

35

10

8

4HK06501525

34.7

42.9

48.8

45

50

8

8

AVY48D**H21

SVY48D**N21

4HK06501025

23.1

31.3

35.1

35

35

8

8

4HK06501525

34.7

43.8

49.6

45

50

8

8

4HK06501825

41.4

51.0

58.0

60

60

6

6

AVY60D**H21

SVY60D**N21

4HK06501025

23.1

33.8

37.6

35

40

8

8

4HK06501525

34.7

46.3

52.1

50

60

8

6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

Models

Heater

Model

Minimum Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

AVY60D**H21

SVY60D**N21

4HK16502525

41.0 / 44.9

31.3 / 36.1

- / -

45 / 45

35 / 40

- / -

8 / 8

8 / 8

- / -

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

Advertising