Devicenet network scanner dvpdnet-sl, 6sending explicit message from ladder diagram – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual

Page 22

Advertising
background image

DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

20

6

Sending Explicit Message from Ladder Diagram

DVPDNET-SL supports the sending of explicit messages through WPL programs.

6.1

The Principle of Explicit Message Sending

DV PDNE T

DV P28SV

RUN

STO P

DeviceNet

RJ12

1

4

VFD-B

IFD9502

Explicit request message

(PLC

DVPDNET-SL)



Explicit response message

(DVPDNET-SL

PLC)



Explicit request message

from master

2

Explicit response message

from slave

3

①: DVP-SV MPU sends out explicit request message to DVPDNET-SL according to WPL program.

②: DVPDNET-SL sends out request message to the target equipment.

③: The target equipment processes the request message and responds DVPDNET-SL.

④: DVP-SV MPU stores the response message from DVPDNET-SL to D register. One explicit message

transmission is therefore completed.

6.2

Structure of Explicit Message

You can edit explicit messages in “explicit request message editing area” and “explicit response message

editing area”. See the table below for the corresponding relation between the two areas and PLC devices. If you

transmit the request message to be sent out to D6250 ~ D6281, DVPDNET-SL will fill the response message to

D6000 ~ D6031.

PLC device

Mapping area

Mapping length

D6000 ~ D6031

Explicit response message editing area

64 bytes

D6250 ~ D6281

Explicit request message editing area

64 bytes

Advertising