DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

4

1.3

I/O Scan List

Item

Explanation

Software screen

Scan

Table

Before DVPDNET-SL starts its operation, you

have to configure its scan list through the

configuration software. The scan list is a list

consisting of the information of slave devices with

data, e.g. slave address, I/O type, I/O data length

and so on, to be exchanged with DVPDNET-SL.

DVPDNET-SL is responsible for managing the

slave devices in the scan list, establishing

connections and exchanging I/O data with them.

DVPDNET-SL will not establish connections and

exchange I/O data with slave devices which are

not configured in the network.

I/O Table

DVPDNET-SL provides an Input Table (380

bytes) and an Output Table (380 bytes) for the

data exchange with slaves. When a slave device is

configured into the scan list, the software will

automatically allocate a I/O data exchange are of

corresponding length to the slave from the

mapping table. The I/O table is the data exchange

interface between the PLC MPU and the slave

device. It corresponds the I/O data in the D

register of the MPU with the I/O data in the slave.

After you configure the network, download the

configured data to DVPDNET-SL, and it will start

the I/O data exchange with the corresponding

slave device according to the configured data

received. Data in Output Table will be sent to the

salve, and data returned from the slave will be

filled into Input Table.

1.4 Specifications

DeviceNet connection

Transmission method

CAN

Electrical isolation

500 VDC

Interface Removable

connector

(5.08mm)

Transmission cable

2-wire twisted shielded cable with 2-wire bus power cable and drain

Communication

Message type

I/O polled, bit-strobe, change of state, cyclic

Baud rates

125 kbps; 250 kbps; 500 kbps

Advertising