APPLIANCES LOCATED IN CONFINED SPACES

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

MIS-1338

NOTE: The inlet and outlet air openings

shall each have a free area of not
less than one square inch per
4,000 BTU per hour (35 square
inches per gallon per hour) of the
total input rating of all
appliances in the enclosure.

FIGURE 15

APPLIANCES LOCATED IN CONFINED SPACES

ALL AIR FROM OUTDOORS

INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC

NOTE: The inlet and outlet air openings

shall each have a free area of not
less than one square inch per 4,000
BTU per hour (35 square inches
per gallon per hour) of the total
input rating of appliances in the
enclosure.