ADJUSTMENT OF THE SENSOR TYPE KS2.EX
Figure 4
Electronic KFA6-SR2-Ex1.W (left) and terminal box KS2.Ex respectively WE77/Ex1
Turn the potentiometer (figure 4) to the left until the LED is OFF.
Turn the potentiometer slowly to the right. After the LED is ON, turn the potentiometer for another
1,5 rotations to the right.