Installation guide, E8950 – Veris Industries E8950 Install User Manual

Page 12

Advertising
background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 12

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

E50C2 and E50C3 Uni-Directional Energy Meter

The E50C2/C3 has 63 data objects and operates at 9600, 19200 or 38400 baud. The E8950 does not support the logging functionality of the E50C3.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Analog_input objects: (Read-only)
kWh Energy: Total

Accumulated Real Energy

AI1

kWh

0

259/260

Resolution is limited by data type (when value exceeds 7

digits, reset more often to maximize resolution)

kW: Total

Total Instantaneous Real Power

AI2

kW

1

261/262

kVAR: Total

Total Instantaneous Reactive Power

AI3

kVAR

1

263/264

KVA: Total

Total Instantaneous Apparent Power

AI4

kVA

1

265/266

PF: Total

Total Instantaneous Power Factor

AI5

PF

0.01

267/268

Volts: L-L Avg

Voltage L-L average of active phases

AI6

Volts

5

269/270

Volts: L-N Avg

Voltage L-N average of active phases

AI7

Volts

5

271/272

Amps: Avg

Current Avg of active phases

AI8

Amps

5

273/274

kW: Ph A

Instantaneous Real Power Phase A

AI9

kW

1

275/276

kW: Ph B

Instantaneous Real Power Phase B

AI10

kW

1

277/278

kW: Ph C

Instantaneous Real Power Phase C

AI11

kW

1

279/280

PF: Ph A

Instantaneous Power Factor Phase A

AI12

PF

0.01

281/282

PF: Ph B

Instantaneous Power Factor Phase B

AI13

PF

0.01

283/284

PF: Ph C

Instantaneous Power Factor Phase C

AI14

PF

0.01

285/286

Volts: Ph A-B Instantaneous Voltage Phase A to Phase B AI15

Volts

5

287/288

Volts: Ph B-C Instantaneous Voltage Phase B to Phase C AI16

Volts

5

289/290

Volts: Ph A-C Instantaneous Voltage Phase A to Phase C AI17

Volts

5

291/292

Volts: Ph A-N Instantaneous Voltage Phase A to Neutral AI18

Volts

5

293/294

Volts: Ph B-N Instantaneous Voltage Phase B to Neutral AI19

Volts

5

295/296

Volts: Ph C-N Instantaneous Voltage Phase C to Neutral AI20

Volts

5

297/298

Amps: Ph A Instantaneous Current Phase A

AI21

Amps

5

299/300

Amps: Ph B Instantaneous Current Phase B

AI22

Amps

5

301/302

Amps: Ph C Instantaneous Current Phase C

AI23

Amps

5

303/304

Reserved Reserved

AI24

n/a

0

305/306

Frequency Instantaneous Frequency

AI25

Hz

0.01

307/308

Returns QNAN if frequency is out of range (or no voltage

input present on Phase A)

kVAh: Total

Accumulated Apparent Energy

Consumption

AI26

kWh

0

309/310

The UNITS property of this object reports kWh because there

is no unit type in this verision of the BACnet standard for

kVARh.

kVARh: Total

Accumulated Reactive Energy

Consumption

AI27

kWh

0

311/312

The UNITS property of this object reports kWh because there

is no unit type in this verision of the BACnet standard for

kVARh.

kVA: Ph A

Instantaneous Apparent Power Phase A

AI28

kVA

1

313/314

kVA: Ph B

Instantaneous Apparent Power Phase B

AI29

kVA

1

315/316

kVA: Ph C

Instantaneous Apparent Power Phase C

AI30

kVA

1

317/318

kVAR: Ph A

Instantaneous Reactive Power Phase A

AI31

kVAR

1

319/320

kVAR: Ph B

Instantaneous Reactive Power Phase B

AI32

kVAR

1

321/322

kVAR: Ph C

Instantaneous Reactive Power Phase C

AI33

kVAR

1

323/324

kW: Demand

Total Real Power Present Demand

AI34

kW

1

325/326

kVAR: Demand Total Reactive Power Present Demand

AI35

kVAR

1

327/328

kVA: Demand Total Apparent Power Present Demand

AI36

kVA

1

329/330

Advertising