E30A042 and E30A142 Branch Circuit Power Meter

The E30A042 and E30A142 meters have 783 data objects per Modbus address and operate at 9600, 19200, or 38400 baud. These meters monitor current, power, demand, and
energy on 42 branch circuits and 4 main circuits (up to 3 phases, plus neutral) and use only one Modbus address.

Due to the capacity limitation of 1000 BACnet data points, the E30Ax84 models and the E31Axxx models are not fully supported. If these products are discovered by the E8950,
they will be automatically mapped to the E30Bxxx profile, which supports a more limited data set.

AV4-AV45 are not writable on E30xxxx solid-core models because the CT size is fixed (at 100 A). Other values written revert to 100 A the next time the meter is scanned.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Analog_Input objects
Frequency: (derived from

Phase A)

Frequency (derived from

Phase A)

AI1

Hz

0.01

600/601

VOLTS L-N: 3ph Ave

Voltage L-L - average of

active phases

AI2

Volts

5

602/603

VOLTS L-L: 3ph Ave

Voltage L-N - average of

active phases

AI3

Volts

5

604/605

VOLTS A-N

Instantaneous Voltage

Ph-A to Neutral

AI4

Volts

5

606/607

VOLTS B-N

Instantaneous Voltage

Ph-B to Neutral

AI5

Volts

5

608/609

VOLTS C-N

Instantaneous Voltage

Ph-C to Neutral

AI6

Volts

5

610/611

VOLTS A-B

Instantaneous Voltage

Phase A to B

AI7

Volts

5

612/613

VOLTS B-C

Instantaneous Voltage

Phase B to C

AI8

Volts

5

614/615

VOLTS A-C

Instantaneous Voltage

Phase A to C

AI9

Volts

5

616/617

kWh Energy: 3ph Total

Real Energy - total of

active phases

AI10

kWh

0

618/619

kW: 3ph Total

Inst Real Power- total of

active phases

AI11

kW

1

620/621

Power Factor: 3ph Total

Inst Power Factor -

average of phases

AI12

PF

0.01

622/623

Amps: 3ph Average

(phases 1,2,3)

Inst Current- average of

active phases

AI13

Amps

5

624/625

kW: Phase 1

Instantaneous Real

Power - Phase 1

AI14

kW

1

626/627

kW: Phase 2

Instantaneous Real

Power - Phase 2

AI15

kW

1

628/629

kW: Phase 3

Instantaneous Real

Power - Phase 3

AI16

kW

1

630/631

Power Factor: Phase 1

Instantaneous Power

Factor - Phase A

AI17

PF

0.01

632/633

Power Factor: Phase 2

Instantaneous Power

Factor - Phase B

AI18

PF

0.01

634/635

Power Factor: Phase 3

Instantaneous Power

Factor - Phase C

AI19

PF

0.01

636/637

Amps: Phase 1

Instantaneous Current -

Phase 1

AI20

Amps

5

638/639

Amps: Phase 2

Instantaneous Current -

Phase 2

AI21

Amps

5

640/641

Amps: Phase 3

Instantaneous Current -

Phase 3

AI22

Amps

5

642/643

Advertising