2 mounting, 1 mounting instructions, 2 compensation of the atmospheric pressure – VEGA D81 METEC Hydrostatic pressure transmitter User Manual

Page 18: 2 compensation of the atmos- pheric pressure

Advertising
background image

18

Pressure transmitter D81 METEC

®

Mounting

2 Mounting

2.1 Mounting instructions

The pressure transmitter can be mounted in
any position. Cable entries must point down-
ward to avoid moisture ingress. For this pur-
pose, the housing can be rotated by 330° in
relation to the mounting part.

An appropriate seal must be used for mount-
ing. This seal is either supplied with the pres-
sure transmitter or must be provided by the
customer.

2.2 Compensation of the atmos-

pheric pressure

On instruments for gauge pressure meas-
urement, the atmospheric pressure is com-
pensated via the breather facility integrated
in the housing.

Pressure transmitter with housing

- via an integrated breather facility (PTFE

insert

1)

), protection IP 66

- via the capillaries of a special cable con-

nected to the terminals, protection IP 67

Pressure transmitter with direct cable
outlet

- via the capillaries of the connected special

cable, protection IP 68

We recommend leading the special cable into
the external connection housing VEGABOX
01 (accessory) and carrying out the pres-
sure compensation via the integrated
breather facility there.

External connection housing

Observe the following instructions:
- as a rule, there must be the same atmos-

pheric pressure on the breather facility as
on the vessel

- the pressure compensation must be done

in a dry environment

- with vertical wall mounting, cable entries

must point downward to avoid moisture
ingress and buildup on the breather facility.

1)

air permeable and moisture blocking