Setup – VEGA D81 METEC Hydrostatic pressure transmitter User Manual

Page 31

Advertising
background image

Pressure transmitter D81 METEC

®

31

Setup

1.2.3.1.1

1.2.3.1.2

Note:

After entering a parameter, push "

ENTER" and then "SEND".

Confirm the message to switch over to manual operation with "

OK".

Confirm the message to reset to automatic operation also with "

OK".

Only then will the adjustment be stored in the sensor and take effect.

Menu windows are displayed but not
supported by the sensor.
Saving of adjustments carried out here is
therefore not possible.

1.4.3.1.3

1.4.3.1.2

Low:

In case of failure, current output
goes to 22 mA

High:

In case of failure, current output
goes to < 3.6 mA

1.4.3.2

1.4.3.1

}

Off
On
Not used
None
Unknown
Special

Sensor signals measured values only on
request
Sensor signals measured values
unrequested

Choice is not supported

1.4.3.2.3

1.4.3.2.4

Leave the burst mode in
OFF position.

Choice is not supported

1.2.3.1.1.1

1.2.3.1.2.1

1.4.3.1.3

1.4.3.1.3.1

Generic: SENSOR
Current applied
process value:

97.112

mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORTENTER

Generic: SENSOR
Current applied
prosess value :96.262
mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: SENSOR
Choose analog output
level

1 4 mA
2 20 mA
3 Other
4 End

ABORTENTER

Generic: SENSOR
WARN - Loop should be
removed from
automatic control

ABORT

OK

Generic: SENSOR
Set the:

1 4 mA
2 20 mA
3 Exit

ABORT ENTER

Generic: SENSOR
Apply new 20 mA input

ABORT

OK

Generic: SENSOR
Current applied
process value: 95.703
mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: SENSOR
Set the:

1 4 mA
2 20 mA
3 EXIT

ABORT ENTER

Generic: SENSOR
Apply new 4 mA input

ABORT OK

Generic: SENSOR
Current applied
process value: 96.549
mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: SENSOR
AO Alrm typ
Lo

EXIT

Generic: SENSOR
HART output

1 Poll addr

0

2 Num req preams 5
3 Burst mode

Off

4 Burst option

HELP SAVE

HOME

Generic: SENSOR
Analog output

1 AO1

19.920 mA

2 AO Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim

HELP SAVE

HOME

Generic: SENSOR
Fld dev output is
fixed at 4.000 mA

ABBR. OK

Generic: SENSOR
Burst mode
Off

Off
On
Not Used
None

ESC

ENTER

Generic: SENSOR
Burst option
*********

PV
% range/current
Process vars/crnt

HELP

ESC

ENTER