Pressure transmitter D81 METEC

®

250

Ri < 250

+

-

PLC

Setup

4.4 Setup with HART

®

handheld

Sensors with electronics versions I, K and L
can be set up with the HART

®

handheld. A

special DD (Data Device Description) is not
necessary. Just connect the HART

®

handheld

to the sensor signal cable after you have
connected the sensor to supply voltage.

Note:

If the resistance of the voltage supply is less
than 250

, a resistor must be looped into the

signal/connection cable during adjustment.
The digital adjustment and communication
signals would otherwise be short-circuited
through insufficient resistance of e.g. the
supply voltage source or the processing
system. Simply connect the adjustment resis-
tor in parallel to the connection socket of the
HART

®

handheld.