VEGA VEGAPULS 65 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-wire User Manual

Page 15

Advertising
background image

W

hen mounting VEGAPULS 65, keep a distance of at least 500 mm

(19.69

in) to the vessel wall. If the sensor is installed in the center of

dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"

Setup").

I

f you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.

1

2

> 500 mm

Fig. 5: Mounting on round vessel tops

1

Reference plane

2

Vessel center or symmetry axis

I

n vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.

Mounting position

VEGAPULS

65 • 4 … 20

mA/HART four-wire

15

4 M

ounting

28442

-EN