Fig. 6: Vessel with conical bottom
D
o not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 7: Inflowing liquid
T
he active part of the antenna, i.e. the conical antenna part should
protrude completely out of the socket.
T
o meet the different socket dimensions, sensors for socket lengths up
to 50, 100 and 250 mm (2, 4, 10 in) are available.
Inflowing medium