3 mounting, 1 mounting instructions, 2 compensation of the atmospheric pressure – VEGA D77 Hydrostatic pressure transmitters User Manual

Page 13: 2 compensation of the atmos- pheric pressure

Advertising
background image

Pressure transmitters D76 and D77

13

1)

Air permeable and moisture-blocking

2)

Cable length 5 m (supplied cable)

3.2 Compensation of the atmos-

pheric pressure

On instruments for gauge pressure meas-
urement, the atmospheric pressure is com-
pensated in different ways, depending on the
pressure transmitter version.

Pressure transmitters with housing

- via an integrated breather facility below the

cable entry (PTFE insert

1)

), protection

IP 66

- via the capillary tubes of the special ca-

ble

2)

, used with the pressure transmitter,

protection IP 67

Pressure transmitters with direct cable
outlet

- via the capillary tubes of the connected

special cable

2)

, protection IP 68

External housing VEGABOX 01

We recommend leading the special cable to
the external housing VEGABOX 01 (acces-
sory) and carrying out the pressure compen-
sation via the integrated breather facility.

Keep the following instructions in mind:
- the same atmospheric pressure as on the

pressure transmitter must also be present
on the external housing VEGABOX 01

- the pressure compensation must be made

in a dry environment

- for vertical wall mounting, the cable entries

must point downwards to avoid moisture
ingress.

Mounting

3 Mounting

3.1 Mounting instructions

Cable entry

The pressure transmitters can be mounted in
any position. Cable entries must point down-
wards to avoid moisture ingress. For this
purpose, the housing can be rotated by 330°
in relation to the mounting part.

A seal, appropriate for connection, must be
used for mounting. This seal is either sup-
plied with the pressure transmitter or must be
provided by the customer.