6 technical data – VEGA VEGASTAB 692 MD User Manual

Page 5

Advertising
background image

VEGASTAB 692 MD

5

Product description

1.6 Technical data

Power supply

Operating voltage/Power consumption

U

nom

= 20 … 250 V AC, 50/60 Hz/approx. 12 VA
= 20 … 72 V DC

Output or measured data input

Number

1 x 24 V output or digital measured data input
for up to 15 sensors

Type of measured data input

active two-wire input, digital (HART

®

protocol),

sensors are powered by VEGASTAB 692 MD

Sensor type

up to 15 VEGA two-wire loop-powered HART

®

sensors in Multidrop mode
(pressure transmitters, ultrasonic and radar
sensors, see chapter "1.5 Sensor choice")

Output voltage

approx. 17 … 24 V DC

Output constant current

max. 60 mA (15 sensors with 4 mA each)

Current limitation

at approx. 200 mA, short-circuit proof

Connection cable

2-wire standard cable (screening is

recommended)

max. cable length

1000 m

max. resistance per wire

15 Ohm

Serial interface (RS 232)

Number

1 x RS 232 via VEGACONNECT 3

Function

communication via modem or PC for data
recording with Visual VEGA (VV) or
sensor adjustment with VEGA Visual Operating
(VVO)

max. cable length

15 m

Interface parameters

9600 baud, no parity, 1 stop bit

Protocol

VEGA specific

Indicating elements

LED in front plate

green: power supply and output voltage on

Ambient conditions

Permissible ambient temperature

-20°C … +60°C

Storage and transport temperature

-40°C … +80°C

Electrical connection

Screw terminals

max. 1.5 mm

2

RS 232 interface (VEGACONNECT 3)

Sub-D 9-pole

Electrical protective measures

Instrument

IP 30

Plug-in socket

IP 20

Protection class

II

Overvoltage category

II