3 electrical connection, 1 connection instructions – VEGA VEGASTAB 692 MD User Manual

Page 8

Advertising
background image

8

VEGASTAB 692 MD

Electrical connection

3 Electrical connection

3.1 Connection instructions

For electrical connection, you should always
observe the following instructions:
- The connection must be made according to

the appropriate national installation stand-
ards (e.g. in Germany acc. to the VDE
regulations).

- The wiring between VEGASTAB 692 MD

and the sensors can be standard two-wire
cable.

- If electromagnetic interference is expected,

the use of screened cable is recom-
mended. The screening must be earthed at
one sensor end.

- The line resistances stated in the technical

data must not be exceeded.

- If overvoltages are expected, we recom-

mend a sensor electronics module with
integrated overvoltage protection or the
installation of VEGA overvoltage arresters.

- When connecting more than one sensor

(max. 15), it is obligatory to connect (be-
fore complete connection) each sensor
individually to VEGASTAB 692 MD and to
assign a different address to each sensor
(1-15) via the software VVO (see chap. "4
Setup").

- Make sure when connecting

VEGACONNECT 3 to a modem that the
modem connection cable for
VEGACONNECT 3 (MODEM.KX) is used.