Vessel with/without cathodic corrosion protection – VEGA Capacitive electrodes EL … User Manual

Page 33

Advertising
background image

Capacitive electrodes EL …

33

A1

A2

E2

E1

1
2

Typ

B62-36G

A

Not-Ex-area (control
room)

either overvoltage protection instrument

Outer
isolation

Screen

Signal conditioning
instrument or safety
barrier

Cathodic corrosion protection
2 … 24 V (object voltage)

Note:
[A] Between control room and overvoltage

protection system a suitable cable, if required
with screen or metal cover, should be used.
Screen or metal cover - if required - must be
only connected to the overvoltage protection
system on the electrode side. In case of
cathodic corrosion protection the cable must be
provided with an outer isolation.

Ex-area

Electrode EL

External
earth
terminal

ELB
2-36

[1]

[1] Overvoltage protection module ELB 2-36

mounted to oscillator (L

i

= 0,15 mH, C

i

= 1,5 nF)

Vessel
Zone 0

Without cathodic corrosion protection: to
potential equalization line

Electrical connection

Vessel with cathodic corrosion protection

E2

E1

A2

A1

A1

A2

E2

E1

1
2

Typ

B62-36G

Typ

B62-36G

B

A

Ex-area

Not-Ex-area (control
room)

either overvoltage protection instrument

Metal housing
without earthing

either overvoltage protection instrument
B62 - 36 G Ex 0 (metal housing) or
B62 - 36 G Ex (plastic housing)
(L

i

= 0,15 mH, C

i

= 1,5 nF)

Electrode EL

Outer
isolation

Outer
isolation

Screen

Screen

Signal conditioning
instrument or safety
barrier

Earth / PA-terminal

Cathodic corrosion protection
2 … 24 V (object voltage)

External
earth
terminals

Note:
[A] and [B] see "Vessel without cathodic corrosion protection“ on
the previous page.

min. 4 mm

2

Cu

Vessel
Zone 0

Capacitive electrode with integral overvoltage protection module

Vessel with/without cathodic corrosion protection