VEGA Capacitive electrodes EL … User Manual

Page 42

Advertising
background image

42

Capacitive electrodes EL …

Diagnosis

Contact 4 against middle pin (1)

The resistance must be 1 M

.

If the resistance is less, this means humidity in the housing or a failure in
the electrode isolation. A possible reason could be a not isolated
electrode which is used in conductive (humid) product.
If the resistance is higher or if the connection is interrupted, the reason is
mainly a bonding failure in the adapter plate or a defect resistor due to
strong electrostatic discharge.
In both cases the electrode must be repaired at VEGA.

Contact 4 against vessel

The connection between contact 4 and the metal vessel (not instrument
hexagon or electrode flange) should be as good as possible. Measure
with an ohmmeter (range very low) the resistance value between contact 4
and the vessel.
• Shortcircuit (0 … 3

), optimum connection

• Resistance > 3

- corrosion on the mounting boss or flange
- probably the mounting boss was covered with Teflon tape or

similar

Check the connection to the vessel. If there is no connection, you can
connect a line from the earth terminal outside to the vessel.
Note that coated flanges must be in any case connected via the earth
terminal to the vessel.

Contact 7 against middle pin (1)

The resistance must be infinite (>10 M

).

If the resistance is less, humidity penetrated or the compensation
capacitor is defect.

Contact 3 against 4

On electrodes without screen the resistance is infinite (>10 M

). On EL 26

the resistance must be 1 M

. In case of lower values, the electrode

isolation is defect or humidity penetrated into the instrument housing.
In case of higher values, a bonding failure in the adapter place is the case
or the resistor is defect.

Contact 4 against 6

In case of older sensors and EL 29 the resistance is infinite, with new
electrodes <3

. In case of values between 3

and 10 M

there is a

defect.

When you cannot find a failure on the electrode, replace the oscillator
against a similar replacement type (if available) or send the electrode for
repair to VEGA.
If the failure does not disappear after inserting of a replacement
electronics, the adjustment on the signal conditioning instrument should be
repeated as the oscillators have certain tolerances.