VEGA VEGABAR 44 4 … 20 mA User Manual

Page 20

Advertising
background image

20

VEGABAR 44 (4 … 20 mA)

Setup

Adjustment taking the current pres-
sure into account (live adjustment)

The live adjustment comprises two steps:
1 Adjustment of zero
2 Adjustment of span

The appropriate output current is displayed
via the DOT-matrix.

1 Adjustment of zero

(e.g. process pressure zero or vessel
empty)

Set the current value to 4.000 mA
with the "+“ or "–“ keys. Then push
the "OK“ key.

2 Adjustment of span

(e.g. process pressure or level at maximum)

Set the current value to 20.000 mA.
with the "+“ or "–“ keys. Then push
the "OK“ key.

Note:

- A modification of zero does not influence

the adjusted span, i.e. final value of the
measuring range will simply be shifted.

- Push "+“ and "-2 simultaneously for stand-

ard adjustment of zero/span. The value
jumps directly to 4 mA/20 mA.

- In the case of a high turn down the "+“ and

"-“ key should generally be pressed simul-
taneously (due to resolution).

- By pushing the "+“ or "–“ keys individually,

the current output remains at the last value,
it takes on the adjusted value only after
storing with the "OK“ key.

- It is also possible to adjust currents for

partial fillings or partial pressures, e.g.
8 mA for 25 % and 16 mA for 75 %. VEGA-
BAR automatically calculates the current
values for 0 % or 100 % (only possible with
a delta >3.3 %).

Adjustment without taking the current
pressure into account (dry adjustment)

Adjustment without pressure comprises four
steps:
1 Selection of the unit in which the adjustment

is to be carried out

2 Offset correction
3 Adjustment of zero
4 Adjustment of span

The offset correction (only in mode gauge
pressure) defines the reference position for
the measurement. It can be carried out:
- before or after the adjustment of zero and

span

- before or after installation of VEGABAR.

VEGABAR must be unpressurised for the
offset correction!

The adjustment without pressure can be
carried out with the sensor installed or not
installed (e.g. workroom). Any currently
existing pressure has no effect on the
adjustment.

1 Selection of the unit

Choose the unit with the "+“ or "–“
key. Save the selected unit with the
"OK“ key.

Zero

4,000

mA

Span

20,000

mA

Adjust

without

press.

Unit

0.0

mbar

psi