1 product description, 1 function and configuration, 2 self-monitoring – VEGA VEGABAR 44 4 … 20 mA User Manual

Page 4

Advertising
background image

4

VEGABAR 44 (4 … 20 mA)

Product description

1 Product description

1.1 Function and configuration

VEGABAR 44 process pressure transmitters
are efficient instruments for process pres-
sure measurement. As pressure sensor
element, the dry ceramic-capacitive measur-
ing cell CERTEC

®

is used. The process pres-

sure causes a capacitance change within the
measuring cell via the diaphragm. This ca-
pacitance change is detected by an ASIC
(Application specific integrated circuit) and
converted into a pressure-proportional signal
by the integrated sensor electronics with
microcontroller. Precise, high-resolution dig-
ital processing of measured data ensures
excellent technical data.

The electronics module is powered by a
separate VEGA signal conditioning
instrument, a stabilised power supply unit or
a PLC (active input). After adjustment, a
standardised 4 … 20 mA current signal is
made available which can be displayed (e.g.
in PLC systems) or further processed.

For carrying out adjustment, the following
alternatives are available:
- adjustment module directly on VEGABAR
- adjustment module in external housing

(VEGADIS 10)

1.2 Self-monitoring

To improve reliability, the functionality of im-
portant electronic components is constantly
checked, and internal parameters such as
sensor value, temperature and operating
voltage are closely monitored.

VEGABAR 40 with ceramic CERTEC

®

measur-

ing cell offers the advantage of continuous
self-monitoring. The measuring and reference
capacitances of the measuring cell constitute
a predefined ratio over the entire measuring
range. Any deviation from these data is a
reliable indicator of a malfunction of the meas-
uring cell.

If errors or malfunctions are detected during
these routines, the fault signal is triggered via
the 4 … 20 mA output (current jump to
3.6 mA or 22 mA).

Advertising