Evaluation, Outputs – VEGA VEGABAR 44 4 … 20 mA User Manual

Page 21

Advertising
background image

VEGABAR 44 (4 … 20 mA)

21

Setup

3 Adjustment of zero

Adjust zero with the "+“ or "–“ key
and save with the "OK“ key.

4 Adjustment of span

Adjust span with the "+“ or "–“ key
and save with the "OK“ key.

Note:

- A modification of zero does not influence

the adjusted span, i.e. final value of the
measuring range will simply be shifted.

- By pushing the "+“ or "–“ keys individually,

the current output remains at the last value,
it takes on the adjusted value only after
storing with the "OK“ key.

Evaluation

Adjustment of the integration time

An integration time t

i

of 0 s … 10 s

can be adjusted with the "+“ or "–“
key. The adjusted value can be

saved with the "OK“ key.

Selection of the indicated unit

The actual measured pressure is
indicated in the DOT-matrix in the
measured value indication. The
respective unit can be chosen with
the "+“ or "–“ key and the "OK“ key
from a list. When choosing the unit
"Scal.“, the following menu items are
available.

Scaling indication

In operating condition, the actual measured
pressure is displayed on the indicating mod-
ule:
- as bar graph with 20 segments
- as 4-digit digital value.

ti

1

s

Zero

0,0

mbar

Span

100,0

mbar

Bar graph and digital value relate to the ad-
justed measuring range and change in
proportion to the current output. Digital
values < –10 % or > 110 % are shown as
flashing figures.

As a result of scaling, the 4 mA or 20 mA
user-specific current output values are
passed to the indicating module as 4-digit
digital values.

Outputs

Current output/Selection of the character-
istics

The current output provides the
actual measured pressure as an
analogue current signal 4 … 20 mA
relating to the adjustment.

The characteristics can also be inverted, e.g.
switched to 20 … 4 mA with the "+“ or "–“ key
and the "OK“ key.

Fault signal

If, during the continuous self-monitoring,
errors, damage or malfunctions in the
measuring cell or the electronics are
detected, a fault signal is triggered via the
current output.

With "+“ or "–“ key and the "OK“
key you can choose if the failure
current should be 22 mA or
3.6 mA.

Unit

0.0

mbar

psi
kPa
%
Scal.
mA

Scaling

indica-

tion

100%=

1000

Decimal

point

888.8

0%=

0

Escape

Current

output

4-20mA

20-4mA

Fault

signal

22mA

3.6mA

Advertising