Failure

Rectification / Measure

VEGATOR 620
functions incorrectly
or not at all

Red failure LED
of VEGATOR 621
or 622 lights

b. Current value > 22 mA

- Check all connections and the connection cable to the sensor.
- Should the red failure lamp continue to light, separate the sensor

from the connection cable and connect a resistor of 2.2 kOhm in its
place.
If the failure lamp extinguishes, the sensor is defective. Check the
connected sensor.

- Should the failure lamp continue to light, reconnect the sensor. Sepa-

rate the signal conditioning instrument from the connection cable and
connect a resistor of 2.2 kOhm to its sensor input.

- Should the failure lamp continue to light, the signal conditioning instru-

ment is defective. In such a case, return the instrument for repair to
VEGA.

- If the failure lamp extinguishes, there is probably a short circuit in the

connection line. Check the connection cable to the sensor.

Note:

A flawlessly operating VEGATOR… has the following switching point values:
Potentiometer position

Sensor current

0

approx. 4 mA

5

approx. 12.5 mA

10

approx. 21 mA

Diagnostics