4 technical data and dimensions – VEGA VEGATOR 622 User Manual

Page 5

Advertising
background image

VEGATOR 620 … 622

5

Product description

1.4 Technical data and dimensions

General data

Power supply

Operating voltage

20 … 72 V DC
20 … 250 V AC, 50/60 Hz (sine)
in case of emergency power supply with curve
form extremely deviating from sine: max.
125 V AC (rectangle)

Power consumption

max. 3 W (3 … 18 VA)

Fuse
- supply range

T 1 A, 250 V

Measurement data input, general

Number

1 current input

Input type

active two-wire input analogue

Range

4 … 20 mA

Sensor

capacitive probes
hydrostatic pressure transmitters
process pressure transmitters

Sensor supply voltage
- VEGATOR 620

24 V DC

- VEGATOR 621, 622

15 … 18 V DC

Switching threshold

4 … 20 mA adjustable

Min. hysteresis
- VEGATOR 620, 621

80 µA

- VEGATOR 622

80 … 16000 µA

Current limitation

at 24 mA, permanently shortcircuit proof

Temperature error

0.05 %/10 K of range

Connection cable

2-wire (standard cable)

Resistance per wire
- VEGATOR 620

max. 250 Ohm

- VEGATOR 621, 622

max. 35 Ohm

off

off

on

VEGATOR 622 double point level
switch

Time t

Max.

Min.

Level

Ex area

Non-Ex area

VEGATOR 622

Double point level switch
with fault monitoring, adjustable switching hysteresis, se-
lectable mode A/B (A = overfill protection, B = dry run pro-
tection) and with adjustable integration time
Input:

1 capacitive electrode
1 hydrostatic pressure transmitter
1 process pressure transmitter

Outputs:

1 relay (spdt)
1 transistor

Approvals:

[EEx ia] IIC,
as part of an overfill protection acc. to WHG

Application:

Min./max. control, overfill protection, dry run
protection

Advertising