6.3 Exchange of the process fitting
The process fitting on VEGABAR 40 can be
easily exchanged.
• First loosen the three screws on the lower
side of the housing with a hexagon socket
size 5.
• Remove the process fitting in the direction
of the arrows from the sensor so that the
connection cable is not damaged.
• Pull out the plug connection.
Plug connection
Hexagon head
screws
Notes
For mounting the other process fitting, pro-
ceed in reverse sequence:
• Insert the cable from the sensor into the
process fitting.
• Plug the process fitting and the sensor
together.
• Screw the process fitting to the sensor,
only use the original screws and plain
washers.
Note:
When switching on (connection of supply
voltage) for the first time after exchanging the
electronic unit, it will take approx. 20 s until
the actual measured value is displayed.