VEGABAR 41 (4 … 20 mA)

27

Instrument modification

6.2 Exchange of electronics

You first have to remove the adjustment mod-
ule, as described in chapter "6.1 Exchange
of adjustment modules“, in order to exchange
the complete electronic module of VEGABAR.

• Remove the ground screw and the two

smaller fixing screws connecting the elec-
tronic unit with the housing

• Pull the electronic unit to the top and pull

out the plug connection

• Proceed in reverse sequence when install-

ing the new electronics module

Note:

No new adjustment is necessary after ex-
changing the electronics module. When
switching on the first time (connection of the
supply voltage) after exchange of the elec-
tronics units, it takes approx. 20 s until the
current measured value is displayed.

Ground
screw

Fixing screw

Fixing screw

Plug
connection

Exchange of the adjustment module

Removal of the adjustment module

Separate VEGABAR from the power
supply

Loosen the screws on the upper side of
the housing and remove the cover or the
display module

Loosen connection cables from the termi-
nals, if necessary pull out the plug con-
nection of the display module

Remove the two screws of the adjustment
module

Remove adjustment module and pull out
plug connection

Insertion of an adjustment module

Plug the plug connection of the new ad-
justment module into the plug-in socket of
the sensor electronics

Fasten the new adjustment module

Reconnect the connection cables, if nec-
essary, also the cable from the display
module

Close cover or display module of VEGA-
BAR

Reconnect VEGABAR to power supply